Skip to content

Menu

Wire size calculator

Enter the current and the one-way distance, and Busbar gives the minimum wire gauge for NM cable, copper THHN in conduit and aluminum side by side. Each size is the larger of what NEC Table 310.16 needs to carry the current (with 240.4(D) for small wire and 125 % for continuous loads) and what keeps voltage drop within your target over that distance. It is free with no sign-up; Pro is US$9 a month for a permit-ready PDF of the calculation. It assumes a 30 °C ambient and up to three current-carrying conductors, use the voltage drop calculator for other conditions, and it is not a licensed electrician's advice.

  • Ampacity and voltage drop
  • Copper and aluminum
  • No sign-up
Wire size calculator
Circuit
A

Breaker rating or load current

ft
%

60 °C column, as 334.80 requires for NM cable

EV chargers, water heaters and similar: sized at 125 %.

Same circuit, other wiring

Copper NM cable (Romex)
10 AWG copper
Copper THHN/THWN-2 in conduit
10 AWG copper
Aluminum XHHW-2 or SER cable
8 AWG aluminum

30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.

Use at least 10 AWG copper

Carries 30.0 A and keeps the drop at 1.55 % over 50 ft, within 3 %.

NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop

Circuit

System
240 V single-phase
Conductor
10 AWG copper
Resistance
1.24 ohm/kft
One-way length
50 ft
Load current
30.0 A
Voltage drop
3.72 V
Voltage drop
1.55 %
Voltage at the load
236.3 V
Conductor ampacity needed at the terminals
30.0 A
10 AWG at the 60 °C column (terminals 60 °C, insulation 60 °C)
30.0 A
10 AWG at 60 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
30.0 A
Overcurrent protection for 10 AWG copper limited to
30 A
Smallest size for ampacity
10 AWG
Smallest size within 3 % drop
12 AWG
Recommended minimum size: the larger of the two
10 AWG copper
  • The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

How it works

  1. 01

    Enter amps and distance

    The breaker rating or load current, and the one-way length of the run in feet.

  2. 02

    Pick the wiring

    NM cable (60 °C), copper THHN in conduit or aluminum, the system voltage and whether the load is continuous.

  3. 03

    Read the gauge

    The minimum size for each kind of wiring, and the full calculation for the one you picked.

Questions

Why does NM cable need a bigger size?

NEC 334.80 limits NM cable to the 60 °C ampacity column, even though its conductors are rated 90 °C. THHN in conduit can use the 75 °C column when the breaker and equipment are marked 75 °C.

Can I hand the result to an inspector?

The page shows every step with its NEC section, so you can copy it into your permit packet for free. Pro (US$9 a month) downloads the same calculation as a PDF with your company, license number, customer and job address.

Do I need to sign up?

No. Every calculator works without an account. You only need one, with a verified email address, to subscribe to Pro.

Hand the inspector a clean calculation

Every calculator is free, with the full step-by-step result and NEC references on the page. Pro is US$9 a month for PDF reports with your company and the job address.