Wire size calculator
Enter the current and the one-way distance, and Busbar gives the minimum wire gauge for NM cable, copper THHN in conduit and aluminum side by side. Each size is the larger of what NEC Table 310.16 needs to carry the current (with 240.4(D) for small wire and 125 % for continuous loads) and what keeps voltage drop within your target over that distance. It is free with no sign-up; Pro is US$9 a month for a permit-ready PDF of the calculation. It assumes a 30 °C ambient and up to three current-carrying conductors, use the voltage drop calculator for other conditions, and it is not a licensed electrician's advice.
- Ampacity and voltage drop
- Copper and aluminum
- No sign-up
Same circuit, other wiring
- Copper NM cable (Romex)
- 10 AWG copper
- Copper THHN/THWN-2 in conduit
- 10 AWG copper
- Aluminum XHHW-2 or SER cable
- 8 AWG aluminum
30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.
Use at least 10 AWG copper
Carries 30.0 A and keeps the drop at 1.55 % over 50 ft, within 3 %.
NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop
Circuit
- System
- 240 V single-phase
- Conductor
- 10 AWG copper
- Resistance
- Ch. 9 Table 8
- 1.24 ohm/kft
- One-way length
- 50 ft
- Load current
- 30.0 A
- Voltage drop
- 3.72 V
- Voltage drop
- 1.55 %
- Voltage at the load
- 236.3 V
- Conductor ampacity needed at the terminals
- 30.0 A
- 10 AWG at the 60 °C column (terminals 60 °C, insulation 60 °C)
- 110.14(C); 310.16
- 30.0 A
- 10 AWG at 60 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
- 310.15(B); 310.15(C)(1)
- 30.0 A
- Overcurrent protection for 10 AWG copper limited to
- 240.4(D)
- 30 A
- Smallest size for ampacity
- 310.16
- 10 AWG
- Smallest size within 3 % drop
- 12 AWG
- Recommended minimum size: the larger of the two
- 10 AWG copper
- The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
How it works
01
Enter amps and distance
The breaker rating or load current, and the one-way length of the run in feet.
02
Pick the wiring
NM cable (60 °C), copper THHN in conduit or aluminum, the system voltage and whether the load is continuous.
03
Read the gauge
The minimum size for each kind of wiring, and the full calculation for the one you picked.
Questions
Why does NM cable need a bigger size?
Can I hand the result to an inspector?
Do I need to sign up?
Common questions
- What size wire for a dryer?
- What size wire for a range?
- What size wire for a water heater?
- What size wire for a hot tub?
- Wire size chart: amps to AWG
- What size wire for a 15 amp circuit?
- What size wire for a 20 amp circuit?
- What size wire for 20 amps at 100 feet?
- What size wire for a 30 amp circuit?
- What size wire for a 40 amp circuit?
- What size wire for a 50 amp circuit?
- All wire, breaker and NEC answers
More NEC calculators
- Dwelling load calculatorService size by the NEC optional method
- EV charger load calculationCan my panel handle an EV charger or heat pump?
- Voltage drop calculatorDrop in volts and percent, and a wire size that carries the load
- Conduit fill calculatorFill percent and the smallest conduit size
- Box fill calculatorIs the electrical box big enough?
- Wire ampacity chartNEC 310.16 with your corrections applied
- Wire gauge chartAWG size, mm², diameter and amps
- Ground wire size calculatorEquipment ground by 250.122, service ground by 250.66
- Transformer sizing calculatorkVA, full-load amps and 450.3(B) breaker sizes
- kVA to amps calculatorSingle- and three-phase, both directions
- Pull box calculatorPull and junction box size by 314.28
- Breaker size calculatorWatts or amps to breaker and wire size
- Panel scheduleCircuit directory and phase loads for a panel
Hand the inspector a clean calculation
Every calculator is free, with the full step-by-step result and NEC references on the page. Pro is US$9 a month for PDF reports with your company and the job address.