Wire size chart: amps to AWG

Find your breaker size in the left column: a 30 A breaker needs 10 AWG copper, a 50 A breaker 6 AWG as NM cable or 8 AWG as THHN in conduit, and a 100 A breaker 3 AWG copper or 1 AWG aluminum. NM cable (Romex) is sized from the 60 °C column of NEC Table 310.16 (334.80), copper THHN and aluminum from the 75 °C column with 75 °C terminals, all with the small-conductor limits of 240.4(D) and at the full breaker rating. Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. A whole-house service may use the 83 % rule of 310.12 and long runs need a larger size for voltage drop, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Minimum wire size by breaker rating
BreakerNM cableTHHN in conduitAluminum
15 A14 AWG14 AWG12 AWG
20 A12 AWG12 AWG10 AWG
25 A10 AWG10 AWG10 AWG
30 A10 AWG10 AWG8 AWG
35 A8 AWG8 AWG8 AWG
40 A8 AWG8 AWG8 AWG
45 A6 AWG8 AWG6 AWG
50 A6 AWG8 AWG6 AWG
60 A4 AWG6 AWG4 AWG
70 A4 AWG4 AWG3 AWG
80 A3 AWG4 AWG2 AWG
90 A2 AWG3 AWG2 AWG
100 A—3 AWG1 AWG
110 A—2 AWG1/0 AWG
125 A—1 AWG2/0 AWG
150 A—1/0 AWG3/0 AWG
175 A—2/0 AWG4/0 AWG
200 A—3/0 AWG250 kcmil
225 A—4/0 AWG300 kcmil
250 A—250 kcmil350 kcmil
300 A—350 kcmil500 kcmil
350 A—500 kcmil700 kcmil
400 A—600 kcmil900 kcmil
Wire size calculator
Circuit
A

Breaker rating or load current

ft
%

60 °C column, as 334.80 requires for NM cable

EV chargers, water heaters and similar: sized at 125 %.

Same circuit, other wiring

Copper NM cable (Romex)
10 AWG copper
Copper THHN/THWN-2 in conduit
10 AWG copper
Aluminum XHHW-2 or SER cable
8 AWG aluminum

30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.

Use at least 10 AWG copper

Carries 30.0 A and keeps the drop at 1.55 % over 50 ft, within 3 %.

NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop

Circuit

System
240 V single-phase
Conductor
10 AWG copper
Resistance
1.24 ohm/kft
One-way length
50 ft
Load current
30.0 A
Voltage drop
3.72 V
Voltage drop
1.55 %
Voltage at the load
236.3 V
Conductor ampacity needed at the terminals
30.0 A
10 AWG at the 60 °C column (terminals 60 °C, insulation 60 °C)
30.0 A
10 AWG at 60 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
30.0 A
Overcurrent protection for 10 AWG copper limited to
30 A
Smallest size for ampacity
10 AWG
Smallest size within 3 % drop
12 AWG
Recommended minimum size: the larger of the two
10 AWG copper
  • The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Why are there no NM cable sizes above 95 A?

NM cable is only made up to 2 AWG copper (334.104), which carries 95 A in its 60 °C column. Larger circuits use SER cable or conductors in conduit.

Is this the same as an ampacity chart?

It is the same table read the other way: the ampacity chart starts from a wire size and gives the amps, this chart starts from the breaker and gives the smallest wire.