What size wire for a water heater?
A 4,500 W, 240 V electric water heater draws 18.75 A, and because 422.13 treats it as a continuous load it needs at least a 25 A circuit, usually 30 A, and a 30 A circuit needs 10 AWG copper NM cable, 10 AWG copper THHN in conduit or 8 AWG aluminum. The size comes from NEC Table 310.16 and 240.4(D) for the full breaker rating, with NM cable at its 60 °C column (334.80). Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Always go by the breaker size on the appliance nameplate, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.
| Wiring | Minimum size |
|---|---|
| 30 A · Copper NM cable (Romex)60 °C column, as 334.80 requires for NM cable | 10 AWG copper |
| 30 A · Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation | 10 AWG copper |
| 30 A · Aluminum XHHW-2 or SER cable75 °C terminals, 90 °C insulation | 8 AWG aluminum |
Same circuit, other wiring
- Copper NM cable (Romex)
- 10 AWG copper
- Copper THHN/THWN-2 in conduit
- 10 AWG copper
- Aluminum XHHW-2 or SER cable
- 8 AWG aluminum
30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.
Use at least 10 AWG copper
Carries 30.0 A and keeps the drop at 1.55 % over 50 ft, within 3 %.
NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop
Circuit
- System
- 240 V single-phase
- Conductor
- 10 AWG copper
- Resistance
- Ch. 9 Table 8
- 1.24 ohm/kft
- One-way length
- 50 ft
- Load current
- 30.0 A
- Voltage drop
- 3.72 V
- Voltage drop
- 1.55 %
- Voltage at the load
- 236.3 V
- Conductor ampacity needed at the terminals
- 30.0 A
- 10 AWG at the 60 °C column (terminals 60 °C, insulation 60 °C)
- 110.14(C); 310.16
- 30.0 A
- 10 AWG at 60 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
- 310.15(B); 310.15(C)(1)
- 30.0 A
- Overcurrent protection for 10 AWG copper limited to
- 240.4(D)
- 30 A
- Smallest size for ampacity
- 310.16
- 10 AWG
- Smallest size within 3 % drop
- 12 AWG
- Recommended minimum size: the larger of the two
- 10 AWG copper
- The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
Questions
Does a water heater need its own circuit?
What about a 5,500 W element?
More answers and calculators
- Dryer wire sizeWhat size wire for a dryer?
- Range wire sizeWhat size wire for a range?
- Hot Tub wire sizeWhat size wire for a hot tub?
- Wire size chartWire size chart: amps to AWG
- 10 gauge wire ampsHow many amps can 10 gauge wire carry?
- Dryer breaker sizeWhat size breaker for a dryer?
- Wire size calculatorAmps and distance in, minimum wire gauge out
- Voltage drop calculatorDrop in volts and percent, and a wire size that carries the load
- All answersEvery wire, breaker, ground and transformer question