What size wire for a range?

Electric ranges usually need a 40 A or 50 A, 240 V circuit, and a 40 A circuit needs 8 AWG copper NM cable, 8 AWG copper THHN in conduit or 8 AWG aluminum. The size comes from NEC Table 310.16 and 240.4(D) for the full breaker rating, with NM cable at its 60 °C column (334.80). Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Always go by the breaker size on the appliance nameplate, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Minimum wire size for a range circuit
WiringMinimum size
40 A · Copper NM cable (Romex)60 °C column, as 334.80 requires for NM cable8 AWG copper
40 A · Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation8 AWG copper
40 A · Aluminum XHHW-2 or SER cable75 °C terminals, 90 °C insulation8 AWG aluminum
50 A · Copper NM cable (Romex)60 °C column, as 334.80 requires for NM cable6 AWG copper
50 A · Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation8 AWG copper
50 A · Aluminum XHHW-2 or SER cable75 °C terminals, 90 °C insulation6 AWG aluminum

Range circuits in practice

Freestanding electric ranges plug into a NEMA 14-50 receptacle, so even a range that only needs 40 A is often wired at 50 A to match the receptacle. Wall ovens and cooktops are usually hardwired through a junction box, each on its own circuit or sharing one under Note 4 of Table 220.55.

Induction ranges draw much the same as radiant ones; the nameplate kW rating, not the cooking technology, sets the circuit.

Wire size calculator
Circuit
A

Breaker rating or load current

ft
%

60 °C column, as 334.80 requires for NM cable

EV chargers, water heaters and similar: sized at 125 %.

Same circuit, other wiring

Copper NM cable (Romex)
8 AWG copper
Copper THHN/THWN-2 in conduit
8 AWG copper
Aluminum XHHW-2 or SER cable
8 AWG aluminum

30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.

Use at least 8 AWG copper

Carries 40.0 A and keeps the drop at 1.30 % over 50 ft, within 3 %.

NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop

Circuit

System
240 V single-phase
Conductor
8 AWG copper
Resistance
0.778 ohm/kft
One-way length
50 ft
Load current
40.0 A
Voltage drop
3.11 V
Voltage drop
1.30 %
Voltage at the load
236.9 V
Conductor ampacity needed at the terminals
40.0 A
8 AWG at the 60 °C column (terminals 60 °C, insulation 60 °C)
40.0 A
8 AWG at 60 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
40.0 A
Smallest size for ampacity
8 AWG
Smallest size within 3 % drop
10 AWG
Recommended minimum size: the larger of the two
8 AWG copper
  • The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Can a cooktop and wall oven share one circuit?

Yes, one counter-mounted cooktop and up to two wall-mounted ovens in the same room may share a branch circuit and be treated as one range for the load calculation (220.55 Note 4).

Do I need a 4-wire cord and circuit?

For new installations, yes: since the 1996 NEC, ranges and dryers are connected with an insulated neutral and a separate equipment grounding conductor (250.140). Older 3-wire circuits may stay where they already exist.