Residential electrical load calculator
Enter the floor area, fixed appliances and heating or cooling, and Busbar sizes the service by the NEC optional method for a one-family dwelling, line by line with the code section. It follows NEC 2020, 2023 or 2026, including the 2026 change to 2 VA per square foot, an 8 kVA first tier and EV chargers at 100 %. The calculation is free with no sign-up; Pro is US$9 a month for a permit-ready PDF with your company and the job address. It covers single-family homes on a 120/240 V or 208Y/120 V service, not multifamily or commercial buildings.
- NEC 2020, 2023 and 2026
- Every step cited
- No sign-up
Calculated load 101.2 A: a 125 A service or larger
24,280 VA at 240 V by the 220.82 optional method. Size the service conductors for this load per 310.12.
NEC 2023 · 220.82 optional method, one-family dwelling · 120/240 V
General loads
- General lighting and receptacles, 2000 ft² × 3 VA
- 220.82(B)(1)
- 6,000 VA
- Small-appliance circuits, 2 × 1,500 VA
- 220.82(B)(2)
- 3,000 VA
- Laundry circuits, 1 × 1,500 VA
- 220.82(B)(2)
- 1,500 VA
- Range, cooktop or wall oven (nameplate)
- 220.82(B)(3)
- 12,000 VA
- Clothes dryer (nameplate)
- 220.82(B)(3)
- 5,000 VA
- Water heater (nameplate)
- 220.82(B)(3)
- 4,500 VA
- Dishwasher (nameplate)
- 220.82(B)(3)
- 1,200 VA
- Total general load
- 33,200 VA
- First 10,000 VA at 100%
- 220.82(B)
- 10,000 VA
- Remainder 23,200 VA at 40%
- 220.82(B)
- 9,280 VA
- General load after demand factors
- 19,280 VA
Heating and air conditioning (largest of)
- Air conditioning and cooling at 100% — largest, used
- 220.82(C)(1)
- 5,000 VA
Service
- Calculated load
- 24,280 VA
- Calculated load ÷ 240 V
- 101.2 A
- Minimum service rating for a one-family dwelling
- 230.79(C)
- 100 A
- The optional method applies only to a one-family dwelling served by a single 120/240-V or 208Y/120-V, three-wire set of service or feeder conductors with an ampacity of 100 A or more (220.82(A)).
- Electric vehicle supply equipment is included in the general load at its nameplate rating.
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
How it works
01
Enter the house
Floor area by outside dimensions, small-appliance and laundry circuits, and the nameplate of each fixed appliance, EV charger included.
02
Add heating and cooling
Air conditioning, heat pump and supplemental heat, or electric space heating. Busbar takes the largest of the 220.82(C) choices.
03
Read the service size
The calculated load in VA and amps and the next standard service size, with each line and its section ready to copy or download.
Questions
Standard or optional method: which one is this?
How are heat pumps counted?
Which NEC edition does Busbar use?
Can I hand the result to an inspector?
Do I need to sign up?
Common questions
- What size wire for a dryer?
- How many amps can 4 gauge wire carry?
- What size breaker for a dryer?
- What size wire for a 60 amp subpanel?
- What size ground wire for a 100 amp service?
- How many outlets can go on a 15 amp circuit?
- What size conduit for 6/3 wire?
- How many amps is a 45 kVA transformer?
- All wire, breaker and NEC answers
More NEC calculators
- EV charger load calculationCan my panel handle an EV charger or heat pump?
- Voltage drop calculatorDrop in volts and percent, and a wire size that carries the load
- Conduit fill calculatorFill percent and the smallest conduit size
- Box fill calculatorIs the electrical box big enough?
- Wire size calculatorAmps and distance in, minimum wire gauge out
- Wire ampacity chartNEC 310.16 with your corrections applied
- Wire gauge chartAWG size, mm², diameter and amps
- Ground wire size calculatorEquipment ground by 250.122, service ground by 250.66
- Transformer sizing calculatorkVA, full-load amps and 450.3(B) breaker sizes
- kVA to amps calculatorSingle- and three-phase, both directions
- Pull box calculatorPull and junction box size by 314.28
- Breaker size calculatorWatts or amps to breaker and wire size
- Panel scheduleCircuit directory and phase loads for a panel
Hand the inspector a clean calculation
Every calculator is free, with the full step-by-step result and NEC references on the page. Pro is US$9 a month for PDF reports with your company and the job address.