What size ground wire for a 100 amp service?
A 100 A home service with 4 AWG copper or 2 AWG aluminum conductors needs an 8 AWG copper or 6 AWG aluminum grounding electrode conductor, and the same 8 AWG copper runs to ground rods, and smaller than 6 AWG it must be protected in a raceway or cable armor (250.64(B)). The size comes from NEC Table 250.66, read by the service-entrance conductors that 310.12 allows at 83 % of the rating, with the rod and concrete-encased electrode limits of 250.66(A) and (B). Busbar's ground wire size calculator below sizes other services and circuits for free; Pro is US$9 a month for a PDF you can attach to a permit. Larger or parallel service conductors move up the table, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.
| Conductor | Minimum size |
|---|---|
| Service-entrance conductors310.12, 83 % of 100 A | 4 AWG copper |
| Grounding electrode conductorTable 250.66: water pipe, building steel | 8 AWG copper |
| Only to ground rods250.66(A) | 8 AWG copper |
| Only to a concrete-encased electrode250.66(B) | 8 AWG copper |
| Main bonding jumperTable 250.102(C)(1) | 8 AWG copper |
Grounding an older 100 A service
Many 100 A services were installed with a single ground rod or only a water-pipe connection. When the service is replaced or upgraded, inspectors usually ask for two rods and a bond to the water pipe.
At this service size the conductor can be 8 AWG copper, but it then has to run in conduit or armor; 6 AWG may run along the building where it is protected from damage.
Grounding electrode conductor: 8 AWG copper or 6 AWG aluminum
Where it runs only to ground rods, 8 AWG copper is enough (250.66(A)).
NEC Table 250.66 · Table 250.102(C)(1)
Service conductors
- Largest ungrounded service-entrance conductor
- 4 AWG copper
- Row of Table 250.66
- Table 250.66
- 2 AWG or smaller copper
Grounding electrode conductor
- To a metal water pipe, building steel or a ground ring
- Table 250.66
- 8 AWG copper or 6 AWG aluminum
- Sole connection to ground rods, pipes or plates
- 250.66(A)
- 8 AWG copper or 6 AWG aluminum
- Sole connection to a concrete-encased electrode
- 250.66(B)
- 8 AWG copper
Bonding jumpers
- Main and supply-side bonding jumper
- Table 250.102(C)(1)
- 8 AWG copper
- Bonding jumpers between electrodes follow the same table and the same rod and concrete-encased limits (250.53(C)). A single ground rod must be supplemented by another electrode unless it measures 25 ohms or less to earth (250.53(A)(2)).
- An 8 AWG grounding electrode conductor must run in a raceway or cable armor; 6 AWG may run along the building where it is not exposed to damage (250.64(B)). Aluminum may not touch masonry or the earth, or end within 18 in of the earth outdoors (250.64(A)).
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
Questions
Can I use 6 AWG instead of 8 AWG?
Is the ground wire the same as the equipment ground?
How many ground rods do I need?
More answers and calculators
- 100 A subpanel ground wireWhat size ground wire for a 100 amp subpanel?
- 200 A service ground wireWhat size ground wire for a 200 amp service?
- Outlets on 20 AHow many outlets can go on a 20 amp circuit?
- Conduit for 6/3 wireWhat size conduit for 6/3 wire?
- Ground wire size calculatorEquipment ground by 250.122, service ground by 250.66
- Wire size calculatorAmps and distance in, minimum wire gauge out
- All answersEvery wire, breaker, ground and transformer question