What size ground wire for a 100 amp service?

A 100 A home service with 4 AWG copper or 2 AWG aluminum conductors needs an 8 AWG copper or 6 AWG aluminum grounding electrode conductor, and the same 8 AWG copper runs to ground rods, and smaller than 6 AWG it must be protected in a raceway or cable armor (250.64(B)). The size comes from NEC Table 250.66, read by the service-entrance conductors that 310.12 allows at 83 % of the rating, with the rod and concrete-encased electrode limits of 250.66(A) and (B). Busbar's ground wire size calculator below sizes other services and circuits for free; Pro is US$9 a month for a PDF you can attach to a permit. Larger or parallel service conductors move up the table, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Grounding and bonding for a 100 A service with 4 AWG copper
ConductorMinimum size
Service-entrance conductors310.12, 83 % of 100 A4 AWG copper
Grounding electrode conductorTable 250.66: water pipe, building steel8 AWG copper
Only to ground rods250.66(A)8 AWG copper
Only to a concrete-encased electrode250.66(B)8 AWG copper
Main bonding jumperTable 250.102(C)(1)8 AWG copper

Grounding an older 100 A service

Many 100 A services were installed with a single ground rod or only a water-pipe connection. When the service is replaced or upgraded, inspectors usually ask for two rods and a bond to the water pipe.

At this service size the conductor can be 8 AWG copper, but it then has to run in conduit or armor; 6 AWG may run along the building where it is protected from damage.

Ground wire size calculator
Service-entrance conductors

Sets are added up by area (Table 250.66)

Grounding electrode conductor: 8 AWG copper or 6 AWG aluminum

Where it runs only to ground rods, 8 AWG copper is enough (250.66(A)).

NEC Table 250.66 · Table 250.102(C)(1)

Service conductors

Largest ungrounded service-entrance conductor
4 AWG copper
Row of Table 250.66
2 AWG or smaller copper

Grounding electrode conductor

To a metal water pipe, building steel or a ground ring
8 AWG copper or 6 AWG aluminum
Sole connection to ground rods, pipes or plates
8 AWG copper or 6 AWG aluminum
Sole connection to a concrete-encased electrode
8 AWG copper

Bonding jumpers

Main and supply-side bonding jumper
8 AWG copper
  • Bonding jumpers between electrodes follow the same table and the same rod and concrete-encased limits (250.53(C)). A single ground rod must be supplemented by another electrode unless it measures 25 ohms or less to earth (250.53(A)(2)).
  • An 8 AWG grounding electrode conductor must run in a raceway or cable armor; 6 AWG may run along the building where it is not exposed to damage (250.64(B)). Aluminum may not touch masonry or the earth, or end within 18 in of the earth outdoors (250.64(A)).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Can I use 6 AWG instead of 8 AWG?

Yes, a larger grounding electrode conductor is always allowed, and 6 AWG copper avoids the conduit that 8 AWG needs (250.64(B)).

Is the ground wire the same as the equipment ground?

No. The grounding electrode conductor connects the service to the earth electrodes and is sized from the service conductors (250.66). The equipment grounding conductors that run with each circuit are sized from the breaker (250.122).

How many ground rods do I need?

One rod must be supplemented by a second electrode unless it measures 25 ohms or less to earth, so most installers drive two rods at least 6 ft apart (250.53(A)). A metal water pipe in contact with the earth for 10 ft or more must also be bonded and supplemented (250.53(D)).