What size ground wire for a 100 amp subpanel?

A 100 A subpanel feeder needs at least an 8 AWG copper or 6 AWG aluminum equipment grounding conductor, run with the feeder and kept apart from the neutral in the subpanel. The size comes from NEC Table 250.122 by the 100 A breaker that protects the feeder, not by the load, and grows in proportion when the feeder wires are upsized for voltage drop (250.122(B)): 2 AWG copper instead of 3 AWG needs a 6 AWG copper ground. Busbar's ground wire size calculator below sizes other services and circuits for free; Pro is US$9 a month for a PDF you can attach to a permit. A subpanel in a detached building also needs its own grounding electrodes (250.32), and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Equipment grounding conductor for a 100 A subpanel
ConductorMinimum size
Feeder conductorsTable 310.16, 75 °C terminals3 AWG copper or 1 AWG aluminum
Equipment grounding conductorTable 250.122, 100 A breaker8 AWG copper
Aluminum grounding conductorTable 250.122, 100 A breaker6 AWG aluminum
Feeder upsized to 2 AWG copper250.122(B), in proportion to the area6 AWG copper
Ground wire size calculator
Circuit or feeder
A

Rating or setting of the device ahead of the conductors

For example upsized for voltage drop: the grounding conductor grows in proportion (250.122(B)).

Minimum equipment grounding conductor: 8 AWG copper

Sized from the rating of the overcurrent device ahead of the circuit, not from the load.

NEC Table 250.122 · 100 A overcurrent device

Circuit

Overcurrent device rating or setting
100 A

Equipment grounding conductor

Table 250.122, devices up to 100 A
8 AWG copper
Minimum equipment grounding conductor
8 AWG copper
  • In parallel runs each raceway or cable gets its own equipment grounding conductor sized from the overcurrent device of the whole run (250.122(F)). For motor circuits the size comes from the motor short-circuit and ground-fault protective device, not the overload (250.122(D)).
  • The table is a minimum: a larger conductor may be needed to clear a fault quickly enough (250.4(A)(5)). A metal raceway or cable armor listed as a grounding conductor can serve instead of a wire (250.118).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Do I need four wires to a subpanel?

Yes. A feeder to a subpanel carries two hots, a neutral and a separate equipment grounding conductor; in the subpanel the neutral bar stays isolated and the grounds bond to the enclosure (250.24(A)(5), 408.40).

Can the conduit be the ground?

Metal conduit such as EMT or rigid conduit is an equipment grounding conductor by itself where its fittings are made up tight (250.118). Many installers still pull a wire ground for reliability.