What size ground wire for a 100 amp subpanel?
A 100 A subpanel feeder needs at least an 8 AWG copper or 6 AWG aluminum equipment grounding conductor, run with the feeder and kept apart from the neutral in the subpanel. The size comes from NEC Table 250.122 by the 100 A breaker that protects the feeder, not by the load, and grows in proportion when the feeder wires are upsized for voltage drop (250.122(B)): 2 AWG copper instead of 3 AWG needs a 6 AWG copper ground. Busbar's ground wire size calculator below sizes other services and circuits for free; Pro is US$9 a month for a PDF you can attach to a permit. A subpanel in a detached building also needs its own grounding electrodes (250.32), and it is not the professional advice of a licensed electrician: check your local electrical code before you install.
| Conductor | Minimum size |
|---|---|
| Feeder conductorsTable 310.16, 75 °C terminals | 3 AWG copper or 1 AWG aluminum |
| Equipment grounding conductorTable 250.122, 100 A breaker | 8 AWG copper |
| Aluminum grounding conductorTable 250.122, 100 A breaker | 6 AWG aluminum |
| Feeder upsized to 2 AWG copper250.122(B), in proportion to the area | 6 AWG copper |
Minimum equipment grounding conductor: 8 AWG copper
Sized from the rating of the overcurrent device ahead of the circuit, not from the load.
NEC Table 250.122 · 100 A overcurrent device
Circuit
- Overcurrent device rating or setting
- 250.122(A)
- 100 A
Equipment grounding conductor
- Table 250.122, devices up to 100 A
- Table 250.122
- 8 AWG copper
- Minimum equipment grounding conductor
- 8 AWG copper
- In parallel runs each raceway or cable gets its own equipment grounding conductor sized from the overcurrent device of the whole run (250.122(F)). For motor circuits the size comes from the motor short-circuit and ground-fault protective device, not the overload (250.122(D)).
- The table is a minimum: a larger conductor may be needed to clear a fault quickly enough (250.4(A)(5)). A metal raceway or cable armor listed as a grounding conductor can serve instead of a wire (250.118).
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
Questions
Do I need four wires to a subpanel?
Can the conduit be the ground?
More answers and calculators
- 100 A service ground wireWhat size ground wire for a 100 amp service?
- 200 A service ground wireWhat size ground wire for a 200 amp service?
- Outlets on 20 AHow many outlets can go on a 20 amp circuit?
- Conduit for 6/3 wireWhat size conduit for 6/3 wire?
- Ground wire size calculatorEquipment ground by 250.122, service ground by 250.66
- Wire size calculatorAmps and distance in, minimum wire gauge out
- All answersEvery wire, breaker, ground and transformer question