What size conduit for 6/3 wire?

For 6/3 run as single conductors, three 6 AWG THHN and a 10 AWG ground, use at least 3/4 in EMT or 3/4 in PVC Schedule 40 (1 in Schedule 80). The four conductors take 0.1732 in² from NEC Chapter 9 Table 5, 32 % of 3/4 in EMT against the 40 % limit of Chapter 9 Table 1 for three or more conductors. Busbar's conduit fill calculator below checks other conductors and conduit types for free; Pro is US$9 a month for a PDF report. 6/3 NM or UF cable pulled whole is figured from its outside diameter on the maker's data sheet (Chapter 9, Note 9), and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

6/3 with ground as THHN: 3 × 6 AWG + 1 × 10 AWG
ConduitSmallest size
EMTChapter 9, Tables 1 and 43/4 in
PVC Schedule 40 / HDPEChapter 9, Tables 1 and 43/4 in
PVC Schedule 80Chapter 9, Tables 1 and 41 in
RMC (rigid metal)Chapter 9, Tables 1 and 43/4 in
FMC (flexible metal)Chapter 9, Tables 1 and 43/4 in
Conduit fill calculator
Raceway

A short raceway between boxes may be filled to 60 %.

Conductors, including grounds

Fits: 32.5 % of 40 % allowed

NEC Chapter 9, Tables 1, 4, 5 and 8 · EMT 3/4 in

Conductors

3 × 6 AWG THHN/THWN-2
0.1521 in²
1 × 10 AWG THHN/THWN-2
0.0211 in²
Total, 4 conductors
0.1732 in²

Raceway

EMT 3/4 in, total area
0.533 in²
Allowed fill for over two conductors
40 %
Allowed area
0.2132 in²
Fill
32.5 %
Smallest EMT that fits
3/4 in
  • Equipment grounding and bonding conductors are counted (Chapter 9, Table 1, Note 3).
  • Check the raceway article for any lower conductor count, and adjust conductor ampacity for more than three current-carrying conductors per 310.15(C)(1).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Can I go up a size to make the pull easier?

Yes, and it is common: the 40 % limit is a maximum. Long runs and several bends are easier in a larger conduit, and 360° of bends is the limit between pull points (358.26 for EMT).

Does the ground wire count?

Yes. Equipment grounding conductors count toward fill like any other conductor (Chapter 9, Table 1, Note 3).