Conduit fill calculator
Pick the conduit type and size and list the conductors, grounds included, and Busbar adds up their areas from NEC Chapter 9 and checks them against the 53, 31 or 40 % limit, or 60 % for a short nipple. It covers EMT, PVC Schedule 40 and 80, RMC, IMC, FMC, LFMC and ENT with THHN/THWN-2, XHHW-2, THW/TW and bare conductors, and finds the smallest size that fits. It is free with no sign-up; Pro is US$9 a month for a PDF report. Cables and compact conductors are not in the tables yet.
- Eight raceway types
- Smallest size that fits
- No sign-up
Fits: 17.5 % of 40 % allowed
NEC Chapter 9, Tables 1, 4, 5 and 8 · EMT 1/2 in
Conductors
- 3 × 12 AWG THHN/THWN-2
- Ch. 9 Table 5
- 0.0399 in²
- 1 × 12 AWG THHN/THWN-2
- Ch. 9 Table 5
- 0.0133 in²
- Total, 4 conductors
- 0.0532 in²
Raceway
- EMT 1/2 in, total area
- Ch. 9 Table 4
- 0.304 in²
- Allowed fill for over two conductors
- Ch. 9 Table 1
- 40 %
- Allowed area
- 0.1216 in²
- Fill
- 17.5 %
- Smallest EMT that fits
- 1/2 in
- Equipment grounding and bonding conductors are counted (Chapter 9, Table 1, Note 3).
- Check the raceway article for any lower conductor count, and adjust conductor ampacity for more than three current-carrying conductors per 310.15(C)(1).
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
How it works
01
Choose the raceway
Conduit or tubing type and trade size; mark it as a nipple if it is 24 in or shorter.
02
List the conductors
Count, size and insulation for each group, equipment grounding conductors included.
03
Read the fill
Total area, fill percent against the allowed limit, and the smallest size of the same raceway that fits.
Questions
Do ground wires count in conduit fill?
Why is the limit 31 % for two wires?
Can I hand the result to an inspector?
Do I need to sign up?
More NEC calculators
- Dwelling load calculatorService size by the NEC optional method
- EV charger load calculationCan my panel handle an EV charger or heat pump?
- Voltage drop calculatorDrop in volts and percent, and a wire size that carries the load
- Box fill calculatorIs the electrical box big enough?
- Wire size calculatorAmps and distance in, minimum wire gauge out
- Wire ampacity chartNEC 310.16 with your corrections applied
- Wire gauge chartAWG size, mm², diameter and amps
- Ground wire size calculatorEquipment ground by 250.122, service ground by 250.66
- Transformer sizing calculatorkVA, full-load amps and 450.3(B) breaker sizes
- kVA to amps calculatorSingle- and three-phase, both directions
- Pull box calculatorPull and junction box size by 314.28
- Breaker size calculatorWatts or amps to breaker and wire size
- Panel scheduleCircuit directory and phase loads for a panel
Hand the inspector a clean calculation
Every calculator is free, with the full step-by-step result and NEC references on the page. Pro is US$9 a month for PDF reports with your company and the job address.