How many outlets can go on a 15 amp circuit?

In a house the NEC sets no limit on receptacles on a 15 A general-purpose circuit, because they are already counted in the general lighting load per square foot; in commercial work each single or duplex receptacle counts as 180 VA, so a 15 A, 120 V circuit (1,800 VA) takes 10. The 180 VA figure is NEC 220.14(I) (120.14 in the 2026 edition), and a 15 A circuit needs at least 14 AWG copper (240.4(D)). Busbar's wire size and box fill calculators check the wire and each box for free; Pro is US$9 a month for PDF reports. Kitchen countertop, bathroom and laundry receptacles need their own 20 A circuits in a home (210.11(C)), and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Receptacles on a 15 A, 120 V circuit
WhereReceptacles
Dwelling, general-purpose220.14(J): counted in the load per square footNo NEC limit
Commercial, 180 VA each1,800 VA ÷ 180 VA (220.14(I))10
Commercial, continuous load80 % of 1,800 VA ÷ 180 VA (210.20(A))8
Wire240.4(D), NM cable or THHN14 AWG copper

Planning 15 amp receptacle circuits

Fifteen-amp circuits suit bedrooms, living rooms, dining rooms and hallways, where lamps, chargers, televisions and other light loads plug in. They should not feed kitchen countertops, bathrooms or laundry receptacles, which need 20 A circuits.

Bedrooms and living areas also need AFCI protection on these circuits in new work (210.12).

Check the wire for a long run with the wire size calculator and whether each box is big enough with the box fill calculator.

Questions

How many outlets can a bedroom circuit have?

There is no NEC limit in a house. Receptacles must be placed so no point along the wall is more than 6 ft from one (210.52(A)), and many electricians keep a bedroom to one or two circuits.

How many outlets do electricians put on a 15 amp circuit at home?

Many plan 8 to 10 so that space heaters, vacuums and other plug-in loads do not trip the breaker, but that is a design choice, not a code rule. One cord-and-plug appliance may use up to 80 % of the rating, 12 A on a 15 A circuit (210.23).

Can lights and outlets share a circuit?

Yes in most rooms of a house. The exceptions are the kitchen small-appliance circuits and the bathroom receptacle circuits, which may not feed lighting or outlets elsewhere (210.52(B), 210.11(C)).