Box fill calculator
Choose the box and count what goes in it, and Busbar adds up the volume NEC 314.16 requires: each conductor, loops counted twice, two allowances per device yoke, one for clamps and one for the grounds plus a quarter for each beyond four. It has every standard metal box from Table 314.16(A) and takes the marked volume of plastic boxes, extension rings and raised covers. It is free with no sign-up; Pro is US$9 a month for a PDF report. Devices and clamps are counted at the largest conductor in the box, which is never less than the code requires.
- All standard metal boxes
- Plastic boxes by marked volume
- No sign-up
Fits: 22.50 in³ needed, 30.3 in³ available
NEC 314.16 · 4 × 2-1/8 square metal box
Volume required
- 6 × 12 AWG conductors (6 × allowance)
- 314.16(B)(1)
- 13.50 in³
- Internal cable clamps (one allowance, 12 AWG) (1 × allowance)
- 314.16(B)(2)
- 2.25 in³
- 1 device yoke(s), two 12 AWG allowances each (2 × allowance)
- 314.16(B)(4)
- 4.50 in³
- 3 equipment grounding conductor(s), one allowance (1 × allowance)
- 314.16(B)(5)
- 2.25 in³
- Total required
- 22.50 in³
Box
- 4 × 2-1/8 square metal box
- 314.16(A)
- 30.3 in³
- Clamp, support-fitting, device and grounding allowances are taken at the largest conductor in the box, which is the same as or more than 314.16(B) requires.
- Conductors that do not leave the box, such as pigtails, are not counted; up to four fixture wires smaller than 14 AWG from a luminaire canopy may be omitted (314.16(B)(1) Exception).
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
How it works
01
Choose the box
A standard metal box from the table, or the cubic inches marked inside a plastic box.
02
Count the conductors
Conductors entering by size, unbroken loops, device yokes, clamps, fixture studs and grounds.
03
Compare the volume
Required cubic inches against the box, with each allowance and its 314.16(B) rule.
Questions
How many 12 AWG wires fit in a 4 × 1-1/2 square box?
Do pigtails count?
Can I hand the result to an inspector?
Do I need to sign up?
More NEC calculators
- Dwelling load calculatorService size by the NEC optional method
- EV charger load calculationCan my panel handle an EV charger or heat pump?
- Voltage drop calculatorDrop in volts and percent, and a wire size that carries the load
- Conduit fill calculatorFill percent and the smallest conduit size
- Wire size calculatorAmps and distance in, minimum wire gauge out
- Wire ampacity chartNEC 310.16 with your corrections applied
- Wire gauge chartAWG size, mm², diameter and amps
- Ground wire size calculatorEquipment ground by 250.122, service ground by 250.66
- Transformer sizing calculatorkVA, full-load amps and 450.3(B) breaker sizes
- kVA to amps calculatorSingle- and three-phase, both directions
- Pull box calculatorPull and junction box size by 314.28
- Breaker size calculatorWatts or amps to breaker and wire size
- Panel scheduleCircuit directory and phase loads for a panel
Hand the inspector a clean calculation
Every calculator is free, with the full step-by-step result and NEC references on the page. Pro is US$9 a month for PDF reports with your company and the job address.