Breaker size calculator

Enter the load in watts or amps with the voltage, and Busbar gives the current, adds 25 % if the load runs three hours or more (NEC 210.20(A)), and picks the next standard breaker size from 240.6(A). It then sizes the wire that breaker can protect from Table 310.16 and 240.4(D), and the equipment grounding conductor from Table 250.122, for NM cable, copper THHN or aluminum. It is free with no sign-up; Pro is US$9 a month for a PDF report. Motors, air conditioners and heat pumps are sized from their nameplate MCA and maximum breaker instead, and it is not a licensed electrician's advice.

  • Watts or amps
  • Wire and ground included
  • No sign-up
Breaker size calculator
Load
W

From the nameplate

Water heaters, EV chargers, lighting left on: sized at 125 %.

60 °C column, as 334.80 requires for NM cable

20 A breaker with 12 AWG copper

Equipment that lists a maximum breaker or fuse on its nameplate (MOCP) must not be protected above it (110.3(B)).

NEC 210.20(A) · 240.6(A) · 240 V single-phase

Load

Load current: 4,500 W ÷ 240 V
18.8 A

Breaker and wire

Smallest standard breaker that carries it
20 A
Wire for that breaker: Copper NM cable (Romex), 60 °C column, as 334.80 requires for NM cable
12 AWG copper
Equipment grounding conductor
12 AWG copper
  • Motor, air-conditioning and heat pump circuits are sized from the nameplate minimum circuit ampacity and maximum overcurrent protection under Articles 430 and 440, not this way. Household ranges may use the demand of Table 220.55 (120.55 in NEC 2026), and storage water heaters of 120 gallons or less are continuous loads (422.13).
  • The wire is sized so its ampacity is at least the breaker rating at 30 °C with no more than three current-carrying conductors; long runs may need a larger size for voltage drop.
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

How it works

  1. 01

    Enter the load

    Watts or amps from the nameplate, the voltage and single- or three-phase.

  2. 02

    Say whether it is continuous

    Loads that run three hours or more, such as water heaters, EV chargers and lighting, are sized at 125 %.

  3. 03

    Read the breaker

    The next standard breaker size, the wire it needs for the wiring you chose and the ground wire.

Questions

What size breaker for a 4,500 watt water heater?

It draws 18.75 A at 240 V; as a continuous load (422.13) that is 23.4 A, so at least a 25 A breaker. Many are wired at 30 A with 10 AWG copper.

Why the 125 % for continuous loads?

A breaker is tested to carry its full rating for a limited time in an enclosure; for loads that run three hours or more, 210.20(A) sizes it at 125 % of the load, which is the same as loading it to no more than 80 %.

Can I hand the result to an inspector?

The page shows every step with its NEC section, so you can copy it into your permit packet for free. Pro (US$9 a month) downloads the same calculation as a PDF with your company, license number, customer and job address.

Do I need to sign up?

No. Every calculator works without an account. You only need one, with a verified email address, to subscribe to Pro.

Hand the inspector a clean calculation

Every calculator is free, with the full step-by-step result and NEC references on the page. Pro is US$9 a month for PDF reports with your company and the job address.