Breaker size calculator
Enter the load in watts or amps with the voltage, and Busbar gives the current, adds 25 % if the load runs three hours or more (NEC 210.20(A)), and picks the next standard breaker size from 240.6(A). It then sizes the wire that breaker can protect from Table 310.16 and 240.4(D), and the equipment grounding conductor from Table 250.122, for NM cable, copper THHN or aluminum. It is free with no sign-up; Pro is US$9 a month for a PDF report. Motors, air conditioners and heat pumps are sized from their nameplate MCA and maximum breaker instead, and it is not a licensed electrician's advice.
- Watts or amps
- Wire and ground included
- No sign-up
20 A breaker with 12 AWG copper
Equipment that lists a maximum breaker or fuse on its nameplate (MOCP) must not be protected above it (110.3(B)).
NEC 210.20(A) · 240.6(A) · 240 V single-phase
Load
- Load current: 4,500 W ÷ 240 V
- 18.8 A
Breaker and wire
- Smallest standard breaker that carries it
- 240.6(A)
- 20 A
- Wire for that breaker: Copper NM cable (Romex), 60 °C column, as 334.80 requires for NM cable
- Table 310.16, 240.4(D)
- 12 AWG copper
- Equipment grounding conductor
- Table 250.122
- 12 AWG copper
- Motor, air-conditioning and heat pump circuits are sized from the nameplate minimum circuit ampacity and maximum overcurrent protection under Articles 430 and 440, not this way. Household ranges may use the demand of Table 220.55 (120.55 in NEC 2026), and storage water heaters of 120 gallons or less are continuous loads (422.13).
- The wire is sized so its ampacity is at least the breaker rating at 30 °C with no more than three current-carrying conductors; long runs may need a larger size for voltage drop.
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
How it works
01
Enter the load
Watts or amps from the nameplate, the voltage and single- or three-phase.
02
Say whether it is continuous
Loads that run three hours or more, such as water heaters, EV chargers and lighting, are sized at 125 %.
03
Read the breaker
The next standard breaker size, the wire it needs for the wiring you chose and the ground wire.
Questions
What size breaker for a 4,500 watt water heater?
Why the 125 % for continuous loads?
Can I hand the result to an inspector?
Do I need to sign up?
Common questions
- What size wire for a dryer?
- What size wire for a range?
- What size wire for a water heater?
- What size wire for a hot tub?
- Wire size chart: amps to AWG
- What size wire for a 15 amp circuit?
- What size wire for a 20 amp circuit?
- What size wire for 20 amps at 100 feet?
- What size wire for a 30 amp circuit?
- What size wire for a 40 amp circuit?
- What size wire for a 50 amp circuit?
- All wire, breaker and NEC answers
More NEC calculators
- Dwelling load calculatorService size by the NEC optional method
- EV charger load calculationCan my panel handle an EV charger or heat pump?
- Voltage drop calculatorDrop in volts and percent, and a wire size that carries the load
- Conduit fill calculatorFill percent and the smallest conduit size
- Box fill calculatorIs the electrical box big enough?
- Wire size calculatorAmps and distance in, minimum wire gauge out
- Wire ampacity chartNEC 310.16 with your corrections applied
- Wire gauge chartAWG size, mm², diameter and amps
- Ground wire size calculatorEquipment ground by 250.122, service ground by 250.66
- Transformer sizing calculatorkVA, full-load amps and 450.3(B) breaker sizes
- kVA to amps calculatorSingle- and three-phase, both directions
- Pull box calculatorPull and junction box size by 314.28
- Panel scheduleCircuit directory and phase loads for a panel
Hand the inspector a clean calculation
Every calculator is free, with the full step-by-step result and NEC references on the page. Pro is US$9 a month for PDF reports with your company and the job address.