What size wire for a 15 amp circuit?

For a 15 A circuit use 14 AWG copper if it is NM cable (Romex), 14 AWG copper THHN/THWN-2 in conduit where the breaker and equipment are rated 75 °C, or 12 AWG aluminum. These come from NEC Table 310.16 with the small-conductor limits of 240.4(D), sizing the wire for the full 15 A breaker rating. Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Long runs need a larger size for voltage drop, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Minimum wire size for a 15 A circuit
WiringMinimum size
Copper NM cable (Romex)60 °C column, as 334.80 requires for NM cable14 AWG copper
Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation14 AWG copper
Aluminum XHHW-2 or SER cable75 °C terminals, 90 °C insulation12 AWG aluminum

What 15 amp circuits feed

Fifteen-amp, 120 V circuits are the usual choice for general lighting and for the receptacles in bedrooms, living rooms, dining rooms and hallways. They also suit bathroom exhaust fans, garage door openers, hardwired smoke alarms and the blower of a gas furnace.

Fifteen amps is the smallest rating for a general-purpose branch circuit, and 14 AWG copper is the smallest building wire normally used for one. Many builders run 20 A circuits everywhere instead so that a vacuum and a space heater on the same circuit do not trip it.

Wire size calculator
Circuit
A

Breaker rating or load current

ft
%

60 °C column, as 334.80 requires for NM cable

EV chargers, water heaters and similar: sized at 125 %.

Same circuit, other wiring

Copper NM cable (Romex)
14 AWG copper
Copper THHN/THWN-2 in conduit
14 AWG copper
Aluminum XHHW-2 or SER cable
12 AWG aluminum

30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.

Use at least 14 AWG copper

Carries 15.0 A and keeps the drop at 1.96 % over 50 ft, within 3 %.

NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop

Circuit

System
240 V single-phase
Conductor
14 AWG copper
Resistance
3.14 ohm/kft
One-way length
50 ft
Load current
15.0 A
Voltage drop
4.71 V
Voltage drop
1.96 %
Voltage at the load
235.3 V
Conductor ampacity needed at the terminals
15.0 A
14 AWG at the 60 °C column (terminals 60 °C, insulation 60 °C)
15.0 A
14 AWG at 60 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
15.0 A
Overcurrent protection for 14 AWG copper limited to
15 A
Smallest size for ampacity
14 AWG
Smallest size within 3 % drop
14 AWG
Recommended minimum size: the larger of the two
14 AWG copper
  • The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Can I swap a 15 amp breaker for a 20 amp one?

Only if every conductor on that circuit is 12 AWG copper or larger. On 14 AWG wire a 20 A breaker lets the wire overheat before it trips (240.4(D)); older homes often mix sizes, so check each box on the run.

Can I use 14 AWG copper for 15 amps?

Only where the conductor's 75 °C ampacity can be used: THHN or similar wire in conduit, with a breaker and equipment marked 75 °C (110.14(C)). NM cable is limited to the 60 °C column (334.80), so it needs 14 AWG.

What about a long run?

Over roughly 50 to 100 feet, voltage drop usually decides the size, not ampacity. Enter the one-way length in the calculator below; it gives the larger of the ampacity size and the voltage drop size.