For a 30 A circuit use 10 AWG copper if it is NM cable (Romex), 10 AWG copper THHN/THWN-2 in conduit where the breaker and equipment are rated 75 °C, or 8 AWG aluminum. These come from NEC Table 310.16 with the small-conductor limits of 240.4(D), sizing the wire for the full 30 A breaker rating. Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Long runs need a larger size for voltage drop, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Minimum wire size for a 30 A circuit
WiringMinimum size
Copper NM cable (Romex)60 °C column, as 334.80 requires for NM cable10 AWG copper
Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation10 AWG copper
Aluminum XHHW-2 or SER cable75 °C terminals, 90 °C insulation8 AWG aluminum

What 30 amp circuits feed

Thirty amps at 240 V is the standard circuit for an electric clothes dryer on a NEMA 14-30 receptacle, for 4,500 W and 5,500 W tank water heaters, for small central air conditioners and heat pumps, and for a Level 2 EV charger set to 24 A.

At 120 V, a 30 A circuit with a TT-30 receptacle is the usual hookup for travel trailers and small RVs. Baseboard heaters on a 30 A, 240 V circuit can total about 5,760 W, because fixed electric space heating counts as a continuous load.

Wire size calculator
Circuit
A

Breaker rating or load current

ft
%

60 °C column, as 334.80 requires for NM cable

EV chargers, water heaters and similar: sized at 125 %.

Same circuit, other wiring

Copper NM cable (Romex)
10 AWG copper
Copper THHN/THWN-2 in conduit
10 AWG copper
Aluminum XHHW-2 or SER cable
8 AWG aluminum

30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.

Use at least 10 AWG copper

Carries 30.0 A and keeps the drop at 1.55 % over 50 ft, within 3 %.

NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop

Circuit

System
240 V single-phase
Conductor
10 AWG copper
Resistance
1.24 ohm/kft
One-way length
50 ft
Load current
30.0 A
Voltage drop
3.72 V
Voltage drop
1.55 %
Voltage at the load
236.3 V
Conductor ampacity needed at the terminals
30.0 A
10 AWG at the 60 °C column (terminals 60 °C, insulation 60 °C)
30.0 A
10 AWG at 60 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
30.0 A
Overcurrent protection for 10 AWG copper limited to
30 A
Smallest size for ampacity
10 AWG
Smallest size within 3 % drop
12 AWG
Recommended minimum size: the larger of the two
10 AWG copper
  • The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Should a 30 amp dryer circuit be 10/2 or 10/3?

10/3 with ground for a dryer: the 14-30 receptacle needs two hots, a neutral for the timer and motor, and a ground. 10/2 with ground is for 240 V loads with no neutral, such as a water heater.

Can I use 10 AWG copper for 30 amps?

Only where the conductor's 75 °C ampacity can be used: THHN or similar wire in conduit, with a breaker and equipment marked 75 °C (110.14(C)). NM cable is limited to the 60 °C column (334.80), so it needs 10 AWG.

What about a long run?

Over roughly 50 to 100 feet, voltage drop usually decides the size, not ampacity. Enter the one-way length in the calculator below; it gives the larger of the ampacity size and the voltage drop size.