What size wire for a 20 amp circuit?

For a 20 A circuit use 12 AWG copper if it is NM cable (Romex), 12 AWG copper THHN/THWN-2 in conduit where the breaker and equipment are rated 75 °C, or 10 AWG aluminum. These come from NEC Table 310.16 with the small-conductor limits of 240.4(D), sizing the wire for the full 20 A breaker rating. Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Long runs need a larger size for voltage drop, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Minimum wire size for a 20 A circuit
WiringMinimum size
Copper NM cable (Romex)60 °C column, as 334.80 requires for NM cable12 AWG copper
Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation12 AWG copper
Aluminum XHHW-2 or SER cable75 °C terminals, 90 °C insulation10 AWG aluminum

What 20 amp circuits feed

In a house, 20 A circuits are required for the kitchen countertop receptacles (at least two small-appliance circuits), the bathroom receptacles, the laundry receptacle and the garage receptacles (210.11(C)). They also suit microwaves, dishwashers, garbage disposals, sump pumps, window air conditioners and portable space heaters.

On a 20 A circuit with two or more receptacles, the receptacles may be rated 15 A or 20 A (Table 210.21(B)(3)); a single receptacle on its own 20 A circuit must be a 20 A one.

Wire size calculator
Circuit
A

Breaker rating or load current

ft
%

60 °C column, as 334.80 requires for NM cable

EV chargers, water heaters and similar: sized at 125 %.

Same circuit, other wiring

Copper NM cable (Romex)
12 AWG copper
Copper THHN/THWN-2 in conduit
12 AWG copper
Aluminum XHHW-2 or SER cable
10 AWG aluminum

30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.

Use at least 12 AWG copper

Carries 20.0 A and keeps the drop at 1.65 % over 50 ft, within 3 %.

NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop

Circuit

System
240 V single-phase
Conductor
12 AWG copper
Resistance
1.98 ohm/kft
One-way length
50 ft
Load current
20.0 A
Voltage drop
3.96 V
Voltage drop
1.65 %
Voltage at the load
236.0 V
Conductor ampacity needed at the terminals
20.0 A
12 AWG at the 60 °C column (terminals 60 °C, insulation 60 °C)
20.0 A
12 AWG at 60 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
20.0 A
Overcurrent protection for 12 AWG copper limited to
20 A
Smallest size for ampacity
12 AWG
Smallest size within 3 % drop
14 AWG
Recommended minimum size: the larger of the two
12 AWG copper
  • The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Why is a 20 amp circuit wired with yellow NM cable?

Manufacturers color-code NM sheathing by size: white for 14 AWG, yellow for 12 AWG and orange for 10 AWG. The color is a convenience, not a code requirement; the size printed on the sheath is what counts.

Can I use 12 AWG copper for 20 amps?

Only where the conductor's 75 °C ampacity can be used: THHN or similar wire in conduit, with a breaker and equipment marked 75 °C (110.14(C)). NM cable is limited to the 60 °C column (334.80), so it needs 12 AWG.

What about a long run?

Over roughly 50 to 100 feet, voltage drop usually decides the size, not ampacity. Enter the one-way length in the calculator below; it gives the larger of the ampacity size and the voltage drop size.