What size wire for 20 amps at 100 feet?

For 20 A at 100 feet one way, use 8 AWG copper at 120 V or 10 AWG copper at 240 V to keep voltage drop within 3 %, even though 12 AWG would carry the current. Busbar takes the larger of the ampacity size (NEC Table 310.16, NM cable at 60 °C) and the voltage drop size (Chapter 9 Table 8). Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. The 3 % target is a recommendation in the informational notes to 210.19, not a mandatory rule, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

20 A at 100 ft one way, copper
WiringMinimum size
120 V, size for ampacityNM cable, 60 °C column12 AWG copper
120 V, size within 3 % drop100 ft one way8 AWG copper
120 V, use at leastlarger of the two8 AWG copper
240 V, use at leastlarger of the two10 AWG copper
Wire size calculator
Circuit
A

Breaker rating or load current

ft
%

60 °C column, as 334.80 requires for NM cable

EV chargers, water heaters and similar: sized at 125 %.

Same circuit, other wiring

Copper NM cable (Romex)
8 AWG copper
Copper THHN/THWN-2 in conduit
8 AWG copper
Aluminum XHHW-2 or SER cable
6 AWG aluminum

30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.

Use at least 8 AWG copper

Carries 20.0 A and keeps the drop at 2.59 % over 100 ft, within 3 %.

NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop

Circuit

System
120 V single-phase
Conductor
8 AWG copper
Resistance
0.778 ohm/kft
One-way length
100 ft
Load current
20.0 A
Voltage drop
3.11 V
Voltage drop
2.59 %
Voltage at the load
116.9 V
Conductor ampacity needed at the terminals
20.0 A
8 AWG at the 60 °C column (terminals 60 °C, insulation 60 °C)
40.0 A
8 AWG at 60 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
40.0 A
Smallest size for ampacity
12 AWG
Smallest size within 3 % drop
8 AWG
Recommended minimum size: the larger of the two
8 AWG copper
  • The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Why is the wire bigger than the breaker needs?

Long runs lose voltage in the wire. A thicker conductor has less resistance, so lights do not dim and motors start properly at the far end.