What size wire for 20 amps at 100 feet?
For 20 A at 100 feet one way, use 8 AWG copper at 120 V or 10 AWG copper at 240 V to keep voltage drop within 3 %, even though 12 AWG would carry the current. Busbar takes the larger of the ampacity size (NEC Table 310.16, NM cable at 60 °C) and the voltage drop size (Chapter 9 Table 8). Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. The 3 % target is a recommendation in the informational notes to 210.19, not a mandatory rule, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.
| Wiring | Minimum size |
|---|---|
| 120 V, size for ampacityNM cable, 60 °C column | 12 AWG copper |
| 120 V, size within 3 % drop100 ft one way | 8 AWG copper |
| 120 V, use at leastlarger of the two | 8 AWG copper |
| 240 V, use at leastlarger of the two | 10 AWG copper |
Same circuit, other wiring
- Copper NM cable (Romex)
- 8 AWG copper
- Copper THHN/THWN-2 in conduit
- 8 AWG copper
- Aluminum XHHW-2 or SER cable
- 6 AWG aluminum
30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.
Use at least 8 AWG copper
Carries 20.0 A and keeps the drop at 2.59 % over 100 ft, within 3 %.
NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop
Circuit
- System
- 120 V single-phase
- Conductor
- 8 AWG copper
- Resistance
- Ch. 9 Table 8
- 0.778 ohm/kft
- One-way length
- 100 ft
- Load current
- 20.0 A
- Voltage drop
- 3.11 V
- Voltage drop
- 2.59 %
- Voltage at the load
- 116.9 V
- Conductor ampacity needed at the terminals
- 20.0 A
- 8 AWG at the 60 °C column (terminals 60 °C, insulation 60 °C)
- 110.14(C); 310.16
- 40.0 A
- 8 AWG at 60 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
- 310.15(B); 310.15(C)(1)
- 40.0 A
- Smallest size for ampacity
- 310.16
- 12 AWG
- Smallest size within 3 % drop
- 8 AWG
- Recommended minimum size: the larger of the two
- 8 AWG copper
- The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
Questions
Why is the wire bigger than the breaker needs?
More answers and calculators
- Wire for 15 ampsWhat size wire for a 15 amp circuit?
- Wire for 20 ampsWhat size wire for a 20 amp circuit?
- Wire for 30 ampsWhat size wire for a 30 amp circuit?
- Wire for 40 ampsWhat size wire for a 40 amp circuit?
- 10 gauge wire ampsHow many amps can 10 gauge wire carry?
- Dryer breaker sizeWhat size breaker for a dryer?
- Wire size calculatorAmps and distance in, minimum wire gauge out
- Voltage drop calculatorDrop in volts and percent, and a wire size that carries the load
- All answersEvery wire, breaker, ground and transformer question