Voltage drop calculator

Pick the system, conductor and size, enter the one-way length and current, and Busbar gives the drop in volts and percent from the NEC Chapter 9 Table 8 resistance and checks that the wire can carry the current under NEC Table 310.16, corrected for terminal rating, ambient temperature, conductors in the raceway and continuous load. The recommended minimum size is the larger of the size that carries the load and the size that stays within your drop target, so a short 40 A run is never sized by voltage drop alone. It is free with no sign-up; Pro is US$9 a month for a schedule of up to 50 circuits in one PDF report. It covers conductors in raceway or cable up to 2,000 V, not free air, and it is not a licensed electrician's advice.

  • Ampacity and drop together
  • Copper and aluminum
  • No sign-up
Voltage drop calculator
Circuit
ft
A
%

3 % for a branch circuit, 5 % feeder plus branch

NM cable is used at 60 °C (334.80).

110.14(C): use 60 °C unless the breaker and equipment are marked 75 °C.

°F

In the same raceway or cable; not grounds

EV chargers, water heaters and similar: conductors are sized at 125 %.

5.28 % drop (6.34 V) — over 3 %

Use at least 8 AWG copper.

NEC Chapter 9 Table 8 resistance at 75 °C · Table 310.16 ampacity with 310.15 corrections · single-phase and DC × 2, three-phase × 1.732

Circuit

System
120 V single-phase
Conductor
12 AWG copper
Resistance
1.98 ohm/kft
One-way length
100 ft
Load current
16.0 A
Voltage drop
6.34 V
Voltage drop
5.28 %
Voltage at the load
113.7 V
Conductor ampacity needed at the terminals
16.0 A
12 AWG at the 75 °C column (terminals 75 °C, insulation 90 °C)
25.0 A
12 AWG at 90 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
30.0 A
Overcurrent protection for 12 AWG copper limited to
20 A
Smallest size for ampacity
12 AWG
Smallest size within 3 % drop
8 AWG
Recommended minimum size: the larger of the two
8 AWG copper
  • The recommended size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D). It does not cover conductors in free air, over 2,000 V, or the other adjustments of 310.15.
  • The NEC recommends, in informational notes to 210.19 and 215.2, no more than 3 % drop on a branch circuit and 5 % on the feeder and branch circuit together; these are not mandatory unless adopted locally. DC resistance from Table 8 ignores reactance; for large conductors on AC, Table 9 effective impedance gives a slightly different result.
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

How it works

  1. 01

    Choose the circuit

    Voltage and phase, copper or aluminum, and the conductor size you plan to use.

  2. 02

    Enter length, load and conditions

    One-way length and load current, then the insulation and terminal ratings, ambient temperature, conductors in the raceway and whether the load is continuous.

  3. 03

    Read the minimum size

    See the drop, the ampacity of your wire at the conditions you set, and the smallest size that both carries the load and stays within your target.

Questions

Does the NEC require 3 % voltage drop?

Not in the main code. Informational notes to 210.19 and 215.2 recommend no more than 3 % on a branch circuit and 5 % on the feeder and branch circuit together. Some codes, such as energy codes, and some jurisdictions make it mandatory.

Does it check that the wire can carry the current?

Yes. The recommended size must carry the load under NEC Table 310.16 at your terminal rating (110.14(C)), with 125 % for continuous loads, ambient temperature correction (310.15(B)), the adjustment for more than three current-carrying conductors (310.15(C)(1)) and the small-conductor limits of 240.4(D). Busbar then takes the larger of that size and the voltage-drop size.

Which formula does it use?

Drop = 2 × length × resistance × current ÷ 1,000 for single-phase and DC, and 1.732 × length × resistance × current ÷ 1,000 for three-phase, with resistance in ohms per 1,000 ft from NEC Chapter 9 Table 8.

Can I hand the result to an inspector?

The page shows every step with its NEC section, so you can copy it into your permit packet for free. Pro (US$9 a month) downloads the same calculation as a PDF with your company, license number, customer and job address.

Do I need to sign up?

No. Every calculator works without an account. You only need one, with a verified email address, to subscribe to Pro.

Hand the inspector a clean calculation

Every calculator is free, with the full step-by-step result and NEC references on the page. Pro is US$9 a month for PDF reports with your company and the job address.