Voltage drop calculator
Pick the system, conductor and size, enter the one-way length and current, and Busbar gives the drop in volts and percent from the NEC Chapter 9 Table 8 resistance and checks that the wire can carry the current under NEC Table 310.16, corrected for terminal rating, ambient temperature, conductors in the raceway and continuous load. The recommended minimum size is the larger of the size that carries the load and the size that stays within your drop target, so a short 40 A run is never sized by voltage drop alone. It is free with no sign-up; Pro is US$9 a month for a schedule of up to 50 circuits in one PDF report. It covers conductors in raceway or cable up to 2,000 V, not free air, and it is not a licensed electrician's advice.
- Ampacity and drop together
- Copper and aluminum
- No sign-up
5.28 % drop (6.34 V) — over 3 %
Use at least 8 AWG copper.
NEC Chapter 9 Table 8 resistance at 75 °C · Table 310.16 ampacity with 310.15 corrections · single-phase and DC × 2, three-phase × 1.732
Circuit
- System
- 120 V single-phase
- Conductor
- 12 AWG copper
- Resistance
- Ch. 9 Table 8
- 1.98 ohm/kft
- One-way length
- 100 ft
- Load current
- 16.0 A
- Voltage drop
- 6.34 V
- Voltage drop
- 5.28 %
- Voltage at the load
- 113.7 V
- Conductor ampacity needed at the terminals
- 16.0 A
- 12 AWG at the 75 °C column (terminals 75 °C, insulation 90 °C)
- 110.14(C); 310.16
- 25.0 A
- 12 AWG at 90 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
- 310.15(B); 310.15(C)(1)
- 30.0 A
- Overcurrent protection for 12 AWG copper limited to
- 240.4(D)
- 20 A
- Smallest size for ampacity
- 310.16
- 12 AWG
- Smallest size within 3 % drop
- 8 AWG
- Recommended minimum size: the larger of the two
- 8 AWG copper
- The recommended size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D). It does not cover conductors in free air, over 2,000 V, or the other adjustments of 310.15.
- The NEC recommends, in informational notes to 210.19 and 215.2, no more than 3 % drop on a branch circuit and 5 % on the feeder and branch circuit together; these are not mandatory unless adopted locally. DC resistance from Table 8 ignores reactance; for large conductors on AC, Table 9 effective impedance gives a slightly different result.
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
How it works
01
Choose the circuit
Voltage and phase, copper or aluminum, and the conductor size you plan to use.
02
Enter length, load and conditions
One-way length and load current, then the insulation and terminal ratings, ambient temperature, conductors in the raceway and whether the load is continuous.
03
Read the minimum size
See the drop, the ampacity of your wire at the conditions you set, and the smallest size that both carries the load and stays within your target.
Questions
Does the NEC require 3 % voltage drop?
Does it check that the wire can carry the current?
Which formula does it use?
Can I hand the result to an inspector?
Do I need to sign up?
Common questions
- What size wire for a dryer?
- What size wire for a range?
- What size wire for a water heater?
- What size wire for a hot tub?
- Wire size chart: amps to AWG
- What size wire for a 15 amp circuit?
- What size wire for a 20 amp circuit?
- What size wire for 20 amps at 100 feet?
- What size wire for a 30 amp circuit?
- What size wire for a 40 amp circuit?
- What size wire for a 50 amp circuit?
- All wire, breaker and NEC answers
More NEC calculators
- Dwelling load calculatorService size by the NEC optional method
- EV charger load calculationCan my panel handle an EV charger or heat pump?
- Conduit fill calculatorFill percent and the smallest conduit size
- Box fill calculatorIs the electrical box big enough?
- Wire size calculatorAmps and distance in, minimum wire gauge out
- Wire ampacity chartNEC 310.16 with your corrections applied
- Wire gauge chartAWG size, mm², diameter and amps
- Ground wire size calculatorEquipment ground by 250.122, service ground by 250.66
- Transformer sizing calculatorkVA, full-load amps and 450.3(B) breaker sizes
- kVA to amps calculatorSingle- and three-phase, both directions
- Pull box calculatorPull and junction box size by 314.28
- Breaker size calculatorWatts or amps to breaker and wire size
- Panel scheduleCircuit directory and phase loads for a panel
Hand the inspector a clean calculation
Every calculator is free, with the full step-by-step result and NEC references on the page. Pro is US$9 a month for PDF reports with your company and the job address.