Transformer sizing calculator
Enter the primary and secondary voltage and the load in kVA or amps, and Busbar picks the smallest standard transformer, gives the primary and secondary full-load current and the largest primary and secondary breaker or fuse that NEC Table 450.3(B) allows. It then sizes the conductors behind those devices from Table 310.16, the primary equipment ground from Table 250.122, and the grounding electrode conductor and bonding jumpers of the separately derived secondary (250.30). It is free with no sign-up; Pro is US$9 a month for a PDF report. It covers transformers of 1000 V and less with conductors at 75 °C terminals and 30 °C ambient, and it is not a licensed electrician's advice.
- Single and three-phase
- 450.3(B) breaker sizes
- No sign-up
75 kVA: 90.2 A primary, 208.2 A secondary
Primary device up to 125 A, secondary device up to 300 A.
NEC 450.3(B) · three-phase, 480 V to 208 V
Size
- Load on the secondary
- 60 kVA
- Smallest standard size that carries it
- 75 kVA
Full-load current
- Primary: 75,000 VA ÷ (480 V × 1.732)
- 90.2 A
- Secondary: 75,000 VA ÷ (208 V × 1.732)
- 208.2 A
Maximum overcurrent protection
- Primary only: 125 % of 90.2 A = 112.8 A, next standard size up
- Table 450.3(B)
- 125 A
- Primary, with secondary protection: 250 % of 90.2 A = 225.5 A, standard size not above
- Table 450.3(B)
- 225 A
- Secondary: 125 % of 208.2 A = 260.2 A, next standard size up
- Table 450.3(B)
- 300 A
Conductors and grounding (copper, 75 °C terminals)
- Primary conductors for the 125 A primary device
- 240.4, Table 310.16
- 1 AWG copper
- Secondary conductors for the 300 A secondary device
- 240.21(C), Table 310.16
- 350 kcmil copper
- Primary equipment grounding conductor
- Table 250.122
- 6 AWG copper
- If the primary device is raised to 225 A (with secondary protection): primary conductors
- 240.4, Table 310.16
- 4/0 AWG copper
- If the primary device is 225 A: primary equipment grounding conductor
- Table 250.122
- 4 AWG copper
- Grounding electrode conductor of the secondary system
- 250.30(A)(5), Table 250.66
- 2 AWG copper or 1/0 AWG aluminum
- System and supply-side bonding jumpers
- 250.30(A)(1)–(2), Table 250.102(C)(1)
- 2 AWG copper
- Table 450.3(B) applies to transformers of 1000 V and less. The NEC does not set the transformer size itself; sizing for the calculated load (Article 220, or 120 in NEC 2026) with room to grow is the usual practice.
- Conductors are sized so their 75 °C ampacity is at least the rating of the device protecting them, with 90 °C insulation at 30 °C and three current-carrying conductors per raceway; above 600 kcmil they are run in parallel sets of 1/0 AWG or larger. If you protect the primary above 125 % under the primary-and-secondary method, size the primary conductors and their equipment grounding conductor for that larger device, as the rows above show.
- Secondary conductors must end in a single overcurrent device that protects them, within the length limits of 240.21(C) (for example 10 ft, or 25 ft with conditions). The secondary of a separately derived system needs its own system bonding jumper and grounding electrode conductor (250.30(A)).
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
How it works
01
Enter the voltages
Single- or three-phase, and the primary and secondary voltage, line to line for three-phase.
02
Enter the load
In kVA or in amps at the secondary, sized at 125 % if it is continuous or you want room to grow; or pick a transformer size.
03
Read the design
Standard kVA size, full-load amps, maximum primary and secondary protection, conductors and grounding, each with its section.
Questions
What size breaker for a 75 kVA transformer?
Does the NEC say how big the transformer must be?
Can I hand the result to an inspector?
Do I need to sign up?
More NEC calculators
- Dwelling load calculatorService size by the NEC optional method
- EV charger load calculationCan my panel handle an EV charger or heat pump?
- Voltage drop calculatorDrop in volts and percent, and a wire size that carries the load
- Conduit fill calculatorFill percent and the smallest conduit size
- Box fill calculatorIs the electrical box big enough?
- Wire size calculatorAmps and distance in, minimum wire gauge out
- Wire ampacity chartNEC 310.16 with your corrections applied
- Wire gauge chartAWG size, mm², diameter and amps
- Ground wire size calculatorEquipment ground by 250.122, service ground by 250.66
- kVA to amps calculatorSingle- and three-phase, both directions
- Pull box calculatorPull and junction box size by 314.28
- Breaker size calculatorWatts or amps to breaker and wire size
- Panel scheduleCircuit directory and phase loads for a panel
Hand the inspector a clean calculation
Every calculator is free, with the full step-by-step result and NEC references on the page. Pro is US$9 a month for PDF reports with your company and the job address.