Ground wire size calculator

Enter the breaker or fuse rating and Busbar gives the minimum equipment grounding conductor from NEC Table 250.122, increased in proportion when the circuit wires are upsized (250.122(B)); or enter the service-entrance conductors for the grounding electrode conductor and main bonding jumper (Tables 250.66 and 250.102(C)(1)). It shows the table row it used and the ground rod and concrete-encased electrode limits of 250.66(A) and (B). It is free with no sign-up; Pro is US$9 a month for a PDF report. Equipment grounds are sized from the overcurrent device, not the load, and it is not a licensed electrician's advice.

  • Equipment and service grounds
  • Upsizing by 250.122(B)
  • No sign-up
Ground wire size calculator
Circuit or feeder
A

Rating or setting of the device ahead of the conductors

For example upsized for voltage drop: the grounding conductor grows in proportion (250.122(B)).

Minimum equipment grounding conductor: 10 AWG copper

Sized from the rating of the overcurrent device ahead of the circuit, not from the load.

NEC Table 250.122 · 60 A overcurrent device

Circuit

Overcurrent device rating or setting
60 A

Equipment grounding conductor

Table 250.122, devices up to 60 A
10 AWG copper
Minimum equipment grounding conductor
10 AWG copper
  • In parallel runs each raceway or cable gets its own equipment grounding conductor sized from the overcurrent device of the whole run (250.122(F)). For motor circuits the size comes from the motor short-circuit and ground-fault protective device, not the overload (250.122(D)).
  • The table is a minimum: a larger conductor may be needed to clear a fault quickly enough (250.4(A)(5)). A metal raceway or cable armor listed as a grounding conductor can serve instead of a wire (250.118).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

How it works

  1. 01

    Choose the conductor

    An equipment grounding conductor for a circuit or feeder, or the grounding electrode conductor of a service.

  2. 02

    Enter the circuit or service

    The breaker or fuse rating, and the phase conductor sizes if they were upsized; or the size and number of parallel service conductors.

  3. 03

    Read the size

    The minimum copper or aluminum size with the table row, the proportional increase and the electrode limits.

Questions

What size ground wire for a 60 amp breaker?

10 AWG copper or 8 AWG aluminum under Table 250.122, which covers devices from 21 A to 60 A in one row. If the circuit conductors are larger than ampacity requires, the ground grows in proportion (250.122(B)).

Why is the service ground sized differently?

The grounding electrode conductor carries fault and lightning current to the earth, so 250.66 sizes it from the service-entrance conductors, with a 6 AWG copper cap for the part that runs only to ground rods. Circuit grounds are sized from the breaker that protects the circuit.

Can I hand the result to an inspector?

The page shows every step with its NEC section, so you can copy it into your permit packet for free. Pro (US$9 a month) downloads the same calculation as a PDF with your company, license number, customer and job address.

Do I need to sign up?

No. Every calculator works without an account. You only need one, with a verified email address, to subscribe to Pro.

Hand the inspector a clean calculation