Ground wire size calculator
Enter the breaker or fuse rating and Busbar gives the minimum equipment grounding conductor from NEC Table 250.122, increased in proportion when the circuit wires are upsized (250.122(B)); or enter the service-entrance conductors for the grounding electrode conductor and main bonding jumper (Tables 250.66 and 250.102(C)(1)). It shows the table row it used and the ground rod and concrete-encased electrode limits of 250.66(A) and (B). It is free with no sign-up; Pro is US$9 a month for a PDF report. Equipment grounds are sized from the overcurrent device, not the load, and it is not a licensed electrician's advice.
- Equipment and service grounds
- Upsizing by 250.122(B)
- No sign-up
Minimum equipment grounding conductor: 10 AWG copper
Sized from the rating of the overcurrent device ahead of the circuit, not from the load.
NEC Table 250.122 · 60 A overcurrent device
Circuit
- Overcurrent device rating or setting
- 250.122(A)
- 60 A
Equipment grounding conductor
- Table 250.122, devices up to 60 A
- Table 250.122
- 10 AWG copper
- Minimum equipment grounding conductor
- 10 AWG copper
- In parallel runs each raceway or cable gets its own equipment grounding conductor sized from the overcurrent device of the whole run (250.122(F)). For motor circuits the size comes from the motor short-circuit and ground-fault protective device, not the overload (250.122(D)).
- The table is a minimum: a larger conductor may be needed to clear a fault quickly enough (250.4(A)(5)). A metal raceway or cable armor listed as a grounding conductor can serve instead of a wire (250.118).
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
How it works
01
Choose the conductor
An equipment grounding conductor for a circuit or feeder, or the grounding electrode conductor of a service.
02
Enter the circuit or service
The breaker or fuse rating, and the phase conductor sizes if they were upsized; or the size and number of parallel service conductors.
03
Read the size
The minimum copper or aluminum size with the table row, the proportional increase and the electrode limits.
Questions
What size ground wire for a 60 amp breaker?
Why is the service ground sized differently?
Can I hand the result to an inspector?
Do I need to sign up?
More NEC calculators
- Dwelling load calculatorService size by the NEC optional method
- EV charger load calculationCan my panel handle an EV charger or heat pump?
- Voltage drop calculatorDrop in volts and percent, and a wire size that carries the load
- Conduit fill calculatorFill percent and the smallest conduit size
- Box fill calculatorIs the electrical box big enough?
- Wire size calculatorAmps and distance in, minimum wire gauge out
- Wire ampacity chartNEC 310.16 with your corrections applied
- Wire gauge chartAWG size, mm², diameter and amps
- Transformer sizing calculatorkVA, full-load amps and 450.3(B) breaker sizes
- kVA to amps calculatorSingle- and three-phase, both directions
- Pull box calculatorPull and junction box size by 314.28
- Breaker size calculatorWatts or amps to breaker and wire size
- Panel scheduleCircuit directory and phase loads for a panel
Hand the inspector a clean calculation
Every calculator is free, with the full step-by-step result and NEC references on the page. Pro is US$9 a month for PDF reports with your company and the job address.