What size ground wire for a 200 amp service?

A 200 A home service with 2/0 AWG copper or 4/0 AWG aluminum conductors needs a 4 AWG copper or 2 AWG aluminum grounding electrode conductor, and the conductor that runs only to ground rods need not be larger than 6 AWG copper (250.66(A)). The size comes from NEC Table 250.66, read by the service-entrance conductors that 310.12 allows at 83 % of the rating, with the rod and concrete-encased electrode limits of 250.66(A) and (B). Busbar's ground wire size calculator below sizes other services and circuits for free; Pro is US$9 a month for a PDF you can attach to a permit. Larger or parallel service conductors move up the table, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Grounding and bonding for a 200 A service with 2/0 AWG copper
ConductorMinimum size
Service-entrance conductors310.12, 83 % of 200 A2/0 AWG copper
Grounding electrode conductorTable 250.66: water pipe, building steel4 AWG copper
Only to ground rods250.66(A)6 AWG copper
Only to a concrete-encased electrode250.66(B)4 AWG copper
Main bonding jumperTable 250.102(C)(1)4 AWG copper

The grounding electrode system of a 200 A service

A typical 200 A service bonds several electrodes together: two ground rods, a metal water pipe where it runs underground, and the concrete-encased electrode (the Ufer) in the footing of a new building.

The conductor to the water pipe or building steel carries the full Table 250.66 size, while the jumpers that run only to rods or the footing may stop at the smaller sizes of 250.66(A) and (B).

Ground wire size calculator
Service-entrance conductors

Sets are added up by area (Table 250.66)

Grounding electrode conductor: 4 AWG copper or 2 AWG aluminum

Where it runs only to ground rods, 6 AWG copper is enough (250.66(A)).

NEC Table 250.66 · Table 250.102(C)(1)

Service conductors

Largest ungrounded service-entrance conductor
2/0 AWG copper
Row of Table 250.66
2/0 or 3/0 AWG copper

Grounding electrode conductor

To a metal water pipe, building steel or a ground ring
4 AWG copper or 2 AWG aluminum
Sole connection to ground rods, pipes or plates
6 AWG copper or 4 AWG aluminum
Sole connection to a concrete-encased electrode
4 AWG copper

Bonding jumpers

Main and supply-side bonding jumper
4 AWG copper
  • Bonding jumpers between electrodes follow the same table and the same rod and concrete-encased limits (250.53(C)). A single ground rod must be supplemented by another electrode unless it measures 25 ohms or less to earth (250.53(A)(2)).
  • An 8 AWG grounding electrode conductor must run in a raceway or cable armor; 6 AWG may run along the building where it is not exposed to damage (250.64(B)). Aluminum may not touch masonry or the earth, or end within 18 in of the earth outdoors (250.64(A)).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Does the water pipe need the 4 AWG conductor?

Yes, if it is the electrode the main conductor runs to: a metal underground water pipe needs the full Table 250.66 size, here 4 AWG copper for 2/0 copper service conductors.

Is the ground wire the same as the equipment ground?

No. The grounding electrode conductor connects the service to the earth electrodes and is sized from the service conductors (250.66). The equipment grounding conductors that run with each circuit are sized from the breaker (250.122).

How many ground rods do I need?

One rod must be supplemented by a second electrode unless it measures 25 ohms or less to earth, so most installers drive two rods at least 6 ft apart (250.53(A)). A metal water pipe in contact with the earth for 10 ft or more must also be bonded and supplemented (250.53(D)).