How many outlets can go on a 20 amp circuit?

In a house the NEC sets no limit on receptacles on a 20 A general-purpose circuit, because they are already counted in the general lighting load per square foot; in commercial work each single or duplex receptacle counts as 180 VA, so a 20 A, 120 V circuit (2,400 VA) takes 13. The 180 VA figure is NEC 220.14(I) (120.14 in the 2026 edition), and a 20 A circuit needs at least 12 AWG copper (240.4(D)). Busbar's wire size and box fill calculators check the wire and each box for free; Pro is US$9 a month for PDF reports. Kitchen countertop, bathroom and laundry receptacles need their own 20 A circuits in a home (210.11(C)), and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Receptacles on a 20 A, 120 V circuit
WhereReceptacles
Dwelling, general-purpose220.14(J): counted in the load per square footNo NEC limit
Commercial, 180 VA each2,400 VA ÷ 180 VA (220.14(I))13
Commercial, continuous load80 % of 2,400 VA ÷ 180 VA (210.20(A))10
Wire240.4(D), NM cable or THHN12 AWG copper

Planning 20 amp receptacle circuits

Twenty-amp receptacle circuits are required in kitchens, bathrooms, laundry rooms and garages, where hair dryers, toasters, kettles and power tools draw the most. A single kitchen appliance can use 1,500 W, so two on one circuit is already most of its 2,400 VA.

In living areas, plan circuits by what will plug in: a home office with computers and a printer, or a room that may get a space heater, deserves its own circuit.

Check the wire for a long run with the wire size calculator and whether each box is big enough with the box fill calculator.

Questions

Can I put 15 amp receptacles on a 20 amp circuit?

Yes, where the circuit has two or more receptacles (Table 210.21(B)(3)). A single receptacle alone on a 20 A circuit must be rated 20 A.

How many outlets do electricians put on a 20 amp circuit at home?

Many plan 8 to 10 so that space heaters, vacuums and other plug-in loads do not trip the breaker, but that is a design choice, not a code rule. One cord-and-plug appliance may use up to 80 % of the rating, 16 A on a 20 A circuit (210.23).

Can lights and outlets share a circuit?

Yes in most rooms of a house. The exceptions are the kitchen small-appliance circuits and the bathroom receptacle circuits, which may not feed lighting or outlets elsewhere (210.52(B), 210.11(C)).