How many outlets can go on a 20 amp circuit?
In a house the NEC sets no limit on receptacles on a 20 A general-purpose circuit, because they are already counted in the general lighting load per square foot; in commercial work each single or duplex receptacle counts as 180 VA, so a 20 A, 120 V circuit (2,400 VA) takes 13. The 180 VA figure is NEC 220.14(I) (120.14 in the 2026 edition), and a 20 A circuit needs at least 12 AWG copper (240.4(D)). Busbar's wire size and box fill calculators check the wire and each box for free; Pro is US$9 a month for PDF reports. Kitchen countertop, bathroom and laundry receptacles need their own 20 A circuits in a home (210.11(C)), and it is not the professional advice of a licensed electrician: check your local electrical code before you install.
| Where | Receptacles |
|---|---|
| Dwelling, general-purpose220.14(J): counted in the load per square foot | No NEC limit |
| Commercial, 180 VA each2,400 VA ÷ 180 VA (220.14(I)) | 13 |
| Commercial, continuous load80 % of 2,400 VA ÷ 180 VA (210.20(A)) | 10 |
| Wire240.4(D), NM cable or THHN | 12 AWG copper |
Planning 20 amp receptacle circuits
Twenty-amp receptacle circuits are required in kitchens, bathrooms, laundry rooms and garages, where hair dryers, toasters, kettles and power tools draw the most. A single kitchen appliance can use 1,500 W, so two on one circuit is already most of its 2,400 VA.
In living areas, plan circuits by what will plug in: a home office with computers and a printer, or a room that may get a space heater, deserves its own circuit.
Check the wire for a long run with the wire size calculator and whether each box is big enough with the box fill calculator.
Questions
Can I put 15 amp receptacles on a 20 amp circuit?
How many outlets do electricians put on a 20 amp circuit at home?
Can lights and outlets share a circuit?
More answers and calculators
- Outlets on 15 AHow many outlets can go on a 15 amp circuit?
- Lights on 15 AHow many lights can go on a 15 amp circuit?
- Conduit for 6/3 wireWhat size conduit for 6/3 wire?
- 75 kVA transformer ampsHow many amps is a 75 kVA transformer?
- Box fill calculatorIs the electrical box big enough?
- Wire size calculatorAmps and distance in, minimum wire gauge out
- All answersEvery wire, breaker, ground and transformer question