Skip to content

Menu

How many lights can go on a 15 amp circuit?

The NEC does not count light fixtures on a 15 A circuit; it limits the load to 1,800 W at 120 V, or 1,440 W (80 %) when the lights stay on for three hours or more and so are a continuous load. That is 144 ten-watt LED bulbs or 24 sixty-watt incandescent bulbs on at least 14 AWG copper, under NEC 210.19(A), 210.20(A) and 240.4(D). Busbar's wire size and box fill calculators check the wire and each box for free; Pro is US$9 a month for PDF reports. In a house general lighting is counted per square foot rather than per fixture, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Lighting load on a 15 A, 120 V circuit
LoadMaximum
Any load15 A × 120 V1,800 W
Lights on 3 hours or more80 % of the rating (210.20(A))1,440 W
10 W LED bulbs1,440 W ÷ 10 W144
60 W incandescent bulbs1,440 W ÷ 60 W24
Wire240.4(D)14 AWG copper

Check the wire for a long run with the wire size calculator and whether each box is big enough with the box fill calculator.

Questions

Should lights go on a 20 amp circuit instead?

They can: a 20 A circuit on 12 AWG wire carries 1,920 W of continuous lighting. Many electricians keep lighting on its own circuits so that a tripped receptacle circuit does not leave a room dark.

Do LED drivers or dimmers change the count?

Use the input watts or volt-amperes on the fixture or driver label, not the bulb equivalent. Dimmers have their own maximum load, often lower for LED than for incandescent bulbs.