How many amps is a 75 kVA transformer?

A 75 kVA three-phase transformer carries 90.2 A at 480 V and 208.2 A at 208 V (amps = 75,000 VA ÷ (volts × 1.732)), and a single-phase 75 kVA transformer 312.5 A at 240 V. From a 480 V primary, NEC Table 450.3(B) allows a primary breaker up to 125 A and a 300 A secondary breaker at 208 V, whose conductors must be at least 350 kcmil copper or 500 kcmil aluminum at 75 °C. Busbar's transformer calculator below sizes other transformers, conductors and grounding for free; Pro is US$9 a month for a PDF you can attach to a permit. These are rated currents, not the load you connect, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Full-load current of a 75 kVA transformer
VoltageAmps or size
Three-phase, 208 V75,000 VA ÷ (208 V × 1.732)208.2 A
Three-phase, 240 V75,000 VA ÷ (240 V × 1.732)180.4 A
Three-phase, 480 V75,000 VA ÷ (480 V × 1.732)90.2 A
Three-phase, 600 V75,000 VA ÷ (600 V × 1.732)72.2 A
Single-phase, 240 V75,000 VA ÷ 240 V312.5 A
Primary breaker, 480 VTable 450.3(B), 125 %125 A
Secondary breaker, 208 VTable 450.3(B), 125 %300 A
Secondary conductors75 °C column of Table 310.16350 kcmil copper

Where 75 kVA transformers are used

A 75 kVA dry-type transformer stepping 480 V down to 208Y/120 V is the workhorse of small commercial buildings: restaurants, retail stores and office floors fed at 480 V use it for receptacles, lighting and small equipment.

Its 208 V secondary commonly feeds a 225 A main breaker panel: 225 A is above the 208 A full-load current and below the 300 A maximum that Table 450.3(B) allows on the secondary.

At this size the unit is floor-mounted on a housekeeping pad in an electrical room, often feeding the restaurant kitchen line, rooftop units on 208 V, or a whole retail floor of lighting and receptacles.

Transformer sizing calculator
Transformer
V

Line to line, e.g. 480

V

Line to line, e.g. 208

kVA

For continuous load or room to grow.

75 kVA: 90.2 A primary, 208.2 A secondary

Primary device up to 125 A, secondary device up to 300 A.

NEC 450.3(B) · three-phase, 480 V to 208 V

Size

Load on the secondary
75 kVA
Transformer chosen
75 kVA

Full-load current

Primary: 75,000 VA ÷ (480 V × 1.732)
90.2 A
Secondary: 75,000 VA ÷ (208 V × 1.732)
208.2 A

Maximum overcurrent protection

Primary only: 125 % of 90.2 A = 112.8 A, next standard size up
125 A
Primary, with secondary protection: 250 % of 90.2 A = 225.5 A, standard size not above
225 A
Secondary: 125 % of 208.2 A = 260.2 A, next standard size up
300 A

Conductors and grounding (copper, 75 °C terminals)

Primary conductors for the 125 A primary device
1 AWG copper
Secondary conductors for the 300 A secondary device
350 kcmil copper
Primary equipment grounding conductor
6 AWG copper
If the primary device is raised to 225 A (with secondary protection): primary conductors
4/0 AWG copper
If the primary device is 225 A: primary equipment grounding conductor
4 AWG copper
Grounding electrode conductor of the secondary system
2 AWG copper or 1/0 AWG aluminum
System and supply-side bonding jumpers
2 AWG copper
  • Table 450.3(B) applies to transformers of 1000 V and less. The NEC does not set the transformer size itself; sizing for the calculated load (Article 220, or 120 in NEC 2026) with room to grow is the usual practice.
  • Conductors are sized so their 75 °C ampacity is at least the rating of the device protecting them, with 90 °C insulation at 30 °C and three current-carrying conductors per raceway; above 600 kcmil they are run in parallel sets of 1/0 AWG or larger. If you protect the primary above 125 % under the primary-and-secondary method, size the primary conductors and their equipment grounding conductor for that larger device, as the rows above show.
  • Secondary conductors must end in a single overcurrent device that protects them, within the length limits of 240.21(C) (for example 10 ft, or 25 ft with conditions). The secondary of a separately derived system needs its own system bonding jumper and grounding electrode conductor (250.30(A)).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

What size panel goes on a 75 kVA transformer?

Commonly a 225 A main breaker panel at 208Y/120 V. The secondary breaker must be at least the 208 A full-load current to carry it and no more than the Table 450.3(B) maximum, and the panel and conductors must be rated for that breaker.

What size breaker for a 75 kVA transformer?

With a 480 V primary and protection on the primary only, up to 125 % of 90.2 A, rounded up to the next standard size: 125 A. With a 300 A secondary main as well, the primary may go up to 250 %, 225 A, but then the primary conductors and their equipment grounding conductor must be sized for that larger breaker.

How much load can it carry?

Up to its rating, 75 kVA, continuously at its rated temperature rise. Many designers load a transformer to about 80 % to leave room for growth and keep it cooler.