How many amps is a 75 kVA transformer?
A 75 kVA three-phase transformer carries 90.2 A at 480 V and 208.2 A at 208 V (amps = 75,000 VA ÷ (volts × 1.732)), and a single-phase 75 kVA transformer 312.5 A at 240 V. From a 480 V primary, NEC Table 450.3(B) allows a primary breaker up to 125 A and a 300 A secondary breaker at 208 V, whose conductors must be at least 350 kcmil copper or 500 kcmil aluminum at 75 °C. Busbar's transformer calculator below sizes other transformers, conductors and grounding for free; Pro is US$9 a month for a PDF you can attach to a permit. These are rated currents, not the load you connect, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.
| Voltage | Amps or size |
|---|---|
| Three-phase, 208 V75,000 VA ÷ (208 V × 1.732) | 208.2 A |
| Three-phase, 240 V75,000 VA ÷ (240 V × 1.732) | 180.4 A |
| Three-phase, 480 V75,000 VA ÷ (480 V × 1.732) | 90.2 A |
| Three-phase, 600 V75,000 VA ÷ (600 V × 1.732) | 72.2 A |
| Single-phase, 240 V75,000 VA ÷ 240 V | 312.5 A |
| Primary breaker, 480 VTable 450.3(B), 125 % | 125 A |
| Secondary breaker, 208 VTable 450.3(B), 125 % | 300 A |
| Secondary conductors75 °C column of Table 310.16 | 350 kcmil copper |
Where 75 kVA transformers are used
A 75 kVA dry-type transformer stepping 480 V down to 208Y/120 V is the workhorse of small commercial buildings: restaurants, retail stores and office floors fed at 480 V use it for receptacles, lighting and small equipment.
Its 208 V secondary commonly feeds a 225 A main breaker panel: 225 A is above the 208 A full-load current and below the 300 A maximum that Table 450.3(B) allows on the secondary.
At this size the unit is floor-mounted on a housekeeping pad in an electrical room, often feeding the restaurant kitchen line, rooftop units on 208 V, or a whole retail floor of lighting and receptacles.
75 kVA: 90.2 A primary, 208.2 A secondary
Primary device up to 125 A, secondary device up to 300 A.
NEC 450.3(B) · three-phase, 480 V to 208 V
Size
- Load on the secondary
- 75 kVA
- Transformer chosen
- 75 kVA
Full-load current
- Primary: 75,000 VA ÷ (480 V × 1.732)
- 90.2 A
- Secondary: 75,000 VA ÷ (208 V × 1.732)
- 208.2 A
Maximum overcurrent protection
- Primary only: 125 % of 90.2 A = 112.8 A, next standard size up
- Table 450.3(B)
- 125 A
- Primary, with secondary protection: 250 % of 90.2 A = 225.5 A, standard size not above
- Table 450.3(B)
- 225 A
- Secondary: 125 % of 208.2 A = 260.2 A, next standard size up
- Table 450.3(B)
- 300 A
Conductors and grounding (copper, 75 °C terminals)
- Primary conductors for the 125 A primary device
- 240.4, Table 310.16
- 1 AWG copper
- Secondary conductors for the 300 A secondary device
- 240.21(C), Table 310.16
- 350 kcmil copper
- Primary equipment grounding conductor
- Table 250.122
- 6 AWG copper
- If the primary device is raised to 225 A (with secondary protection): primary conductors
- 240.4, Table 310.16
- 4/0 AWG copper
- If the primary device is 225 A: primary equipment grounding conductor
- Table 250.122
- 4 AWG copper
- Grounding electrode conductor of the secondary system
- 250.30(A)(5), Table 250.66
- 2 AWG copper or 1/0 AWG aluminum
- System and supply-side bonding jumpers
- 250.30(A)(1)–(2), Table 250.102(C)(1)
- 2 AWG copper
- Table 450.3(B) applies to transformers of 1000 V and less. The NEC does not set the transformer size itself; sizing for the calculated load (Article 220, or 120 in NEC 2026) with room to grow is the usual practice.
- Conductors are sized so their 75 °C ampacity is at least the rating of the device protecting them, with 90 °C insulation at 30 °C and three current-carrying conductors per raceway; above 600 kcmil they are run in parallel sets of 1/0 AWG or larger. If you protect the primary above 125 % under the primary-and-secondary method, size the primary conductors and their equipment grounding conductor for that larger device, as the rows above show.
- Secondary conductors must end in a single overcurrent device that protects them, within the length limits of 240.21(C) (for example 10 ft, or 25 ft with conditions). The secondary of a separately derived system needs its own system bonding jumper and grounding electrode conductor (250.30(A)).
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
Questions
What size panel goes on a 75 kVA transformer?
What size breaker for a 75 kVA transformer?
How much load can it carry?
More answers and calculators
- 45 kVA transformer ampsHow many amps is a 45 kVA transformer?
- Wire for 50 ampsWhat size wire for a 50 amp circuit?
- 10 gauge wire ampsHow many amps can 10 gauge wire carry?
- Transformer sizing calculatorkVA, full-load amps and 450.3(B) breaker sizes
- kVA to amps calculatorSingle- and three-phase, both directions
- All answersEvery wire, breaker, ground and transformer question