kVA to amps calculator

Enter kVA and the voltage, and Busbar gives the current: amps = kVA × 1,000 ÷ volts for single-phase, or ÷ (volts × 1.732) for three-phase with the line-to-line voltage; switch the direction to get kVA from amps. Below the result is the full-load current of every standard transformer size at your voltage, so a 75 kVA three-phase transformer reads 208.2 A at 208 V. It is free with no sign-up; Pro is US$9 a month to download the table as a PDF. Full-load current is the rated output, not the actual load; for breakers and wire use the transformer sizing calculator.

  • Both directions
  • Standard sizes table
  • No sign-up
kVA to amps calculator
Convert
kVA
V

Line to line

75 kVA = 208.2 A at 208 V three-phase

Amps = kVA × 1,000 ÷ (volts × 1.732). The reverse: kVA = amps × volts × 1.732 ÷ 1,000.

three-phase, 208 V

Conversion

75,000 VA ÷ (208 V × 1.732)
208.2 A

Full-load amps of standard three-phase sizes at 208 V

3 kVA
8.3 A
6 kVA
16.7 A
9 kVA
25.0 A
15 kVA
41.6 A
30 kVA
83.3 A
45 kVA
124.9 A
75 kVA
208.2 A
112.5 kVA
312.3 A
150 kVA
416.4 A
225 kVA
624.5 A
300 kVA
832.7 A
500 kVA
1387.9 A
750 kVA
2081.8 A
1,000 kVA
2775.7 A
1,500 kVA
4163.6 A
2,000 kVA
5551.4 A
2,500 kVA
6939.3 A
  • Full-load current is the rated output, not the load you connect. For a three-phase system use the line-to-line voltage (208, 480); 1.732 is the square root of 3 (1.7321).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

How it works

  1. 01

    Choose the direction

    kVA to amps, or amps to kVA.

  2. 02

    Enter voltage and phase

    Line-to-line voltage for three-phase (208, 480), or the circuit voltage for single-phase.

  3. 03

    Read the result

    The current or kVA, and the full-load amps of standard transformer sizes at that voltage.

Questions

Why divide by 1.732 for three-phase?

In a balanced three-phase system the power is volts × amps × √3 (1.732), using the line-to-line voltage. Using 120 or 277 V line-to-neutral instead would need a factor of 3.

Is kVA the same as kW?

Only at a power factor of 1. kW = kVA × power factor, so a load with a power factor of 0.8 draws 1.25 kVA for every kW. Transformers and generators are rated in kVA because the current, not the real power, heats them.

Do I need to sign up?

No. Every calculator works without an account. You only need one, with a verified email address, to subscribe to Pro.

Hand the inspector a clean calculation

Every calculator is free, with the full step-by-step result and NEC references on the page. Pro is US$9 a month for PDF reports with your company and the job address.