Pull box sizing calculator

Choose a straight, angle or U pull and enter the raceways on each wall, and Busbar gives the minimum box dimensions by NEC 314.28(A): eight times the largest trade size for a straight pull, and for angle and U pulls six times the largest raceway in the row plus the sum of the others on the same wall. It also gives the minimum spacing between entries of the same conductors and checks a box you enter. It is free with no sign-up; Pro is US$9 a month for a PDF report. It applies to conductors 4 AWG and larger, smaller ones are sized by box fill, and it is not a licensed electrician's advice.

  • Straight, angle and U pulls
  • Checks your box
  • No sign-up
Pull box calculator

Conductors 4 AWG and larger. Enter one row of raceways per wall.

Wall A
Wall B
Box to check (optional)
in
in

Minimum: 22 in × 22 in

Keep the raceway entries of the same conductors at least 18 in apart, measured between their nearest edges.

NEC 314.28(A) · Angle pull or splice, conductors 4 AWG and larger

Raceways in one row

Wall A
1 × 3 in, 2 × 2 in
Wall B
1 × 3 in, 2 × 2 in

Minimum dimensions

Wall A to the opposite wall: 6 × 3 in + 4 in
22 in
Wall B to the opposite wall: 6 × 3 in + 4 in
22 in
Between the entries of the same conductors: 6 × the larger raceway
18 in or more
  • Each row of raceways is calculated on its own and the row that needs the largest distance decides. The rule uses the trade size of the raceway, not its outside diameter.
  • A smaller box is allowed only where it is listed and permanently marked for the number and size of conductors it holds (314.28(A)(3)). For conductors smaller than 4 AWG the box is sized by volume under 314.16.
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

How it works

  1. 01

    Choose the pull

    Straight through, an angle pull or splice, or a U pull that enters and leaves on the same wall.

  2. 02

    List the raceways

    Count and trade size of the raceways in one row on each wall.

  3. 03

    Read the box size

    Each minimum dimension with its formula, the spacing between entries, and whether your box is big enough.

Questions

How big a pull box for 3 inch conduit?

For a straight pull, at least 24 in long (8 × 3). For an angle pull with one 3 in conduit on each wall, at least 18 in from each entry wall to the opposite wall (6 × 3), plus the trade sizes of any other raceways in the same row.

Does it use the conduit outside diameter?

No. 314.28 multiplies the trade size, so 2 in conduit counts as 2 whatever its actual diameter.

Can I hand the result to an inspector?

The page shows every step with its NEC section, so you can copy it into your permit packet for free. Pro (US$9 a month) downloads the same calculation as a PDF with your company, license number, customer and job address.

Do I need to sign up?

No. Every calculator works without an account. You only need one, with a verified email address, to subscribe to Pro.

Hand the inspector a clean calculation

Every calculator is free, with the full step-by-step result and NEC references on the page. Pro is US$9 a month for PDF reports with your company and the job address.