Choose a straight, angle or U pull and enter the raceways on each wall, and Busbar gives the minimum box dimensions by NEC 314.28(A): eight times the largest trade size for a straight pull, and for angle and U pulls six times the largest raceway in the row plus the sum of the others on the same wall. It also gives the minimum spacing between entries of the same conductors and checks a box you enter. It is free with no sign-up; Pro is US$9 a month for a PDF report. It applies to conductors 4 AWG and larger, smaller ones are sized by box fill, and it is not a licensed electrician's advice.
- Straight, angle and U pulls
- Checks your box
- No sign-up
Conductors 4 AWG and larger. Enter one row of raceways per wall.
Minimum: 22 in × 22 in
Keep the raceway entries of the same conductors at least 18 in apart, measured between their nearest edges.
NEC 314.28(A) · Angle pull or splice, conductors 4 AWG and larger
Raceways in one row
- Wall A
- 1 × 3 in, 2 × 2 in
- Wall B
- 1 × 3 in, 2 × 2 in
Minimum dimensions
- Wall A to the opposite wall: 6 × 3 in + 4 in
- 314.28(A)(2)
- 22 in
- Wall B to the opposite wall: 6 × 3 in + 4 in
- 314.28(A)(2)
- 22 in
- Between the entries of the same conductors: 6 × the larger raceway
- 314.28(A)(2)
- 18 in or more
- Each row of raceways is calculated on its own and the row that needs the largest distance decides. The rule uses the trade size of the raceway, not its outside diameter.
- A smaller box is allowed only where it is listed and permanently marked for the number and size of conductors it holds (314.28(A)(3)). For conductors smaller than 4 AWG the box is sized by volume under 314.16.
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
How it works
01
Choose the pull
Straight through, an angle pull or splice, or a U pull that enters and leaves on the same wall.
02
List the raceways
Count and trade size of the raceways in one row on each wall.
03
Read the box size
Each minimum dimension with its formula, the spacing between entries, and whether your box is big enough.
Questions
How big a pull box for 3 inch conduit?
Does it use the conduit outside diameter?
Can I hand the result to an inspector?
Do I need to sign up?
Common questions
More NEC calculators
- Dwelling load calculatorService size by the NEC optional method
- EV charger load calculationCan my panel handle an EV charger or heat pump?
- Voltage drop calculatorDrop in volts and percent, and a wire size that carries the load
- Conduit fill calculatorFill percent and the smallest conduit size
- Box fill calculatorIs the electrical box big enough?
- Wire size calculatorAmps and distance in, minimum wire gauge out
- Wire ampacity chartNEC 310.16 with your corrections applied
- Wire gauge chartAWG size, mm², diameter and amps
- Ground wire size calculatorEquipment ground by 250.122, service ground by 250.66
- Transformer sizing calculatorkVA, full-load amps and 450.3(B) breaker sizes
- kVA to amps calculatorSingle- and three-phase, both directions
- Breaker size calculatorWatts or amps to breaker and wire size
- Panel scheduleCircuit directory and phase loads for a panel
Hand the inspector a clean calculation
Every calculator is free, with the full step-by-step result and NEC references on the page. Pro is US$9 a month for PDF reports with your company and the job address.