Wire gauge chart
Every AWG and kcmil size from 14 AWG to 1000 kcmil with its area in square millimetres, its stranded diameter from NEC Chapter 9 Table 8, and its ampacity at 60, 75 and 90 °C from Table 310.16, for copper or aluminum. The usable column applies your terminal rating, ambient temperature and conductors in the raceway, and the 240.4(D) breaker limit for small wire. It is free with no sign-up; Pro is US$9 a month to download it as a PDF. Diameters are for the bare stranded conductor without insulation, and it is not a licensed electrician's advice.
- AWG to mm²
- Diameter and ampacity
- No sign-up
| Size | mm² | Diameter | 60 °C | 75 °C | 90 °C | Corrected | Usable |
|---|---|---|---|---|---|---|---|
| 14 AWG | 2.08 | 0.073 in | 15 | 20 | 25 | 25 | 20 A(max 15 A breaker) |
| 12 AWG | 3.31 | 0.092 in | 20 | 25 | 30 | 30 | 25 A(max 20 A breaker) |
| 10 AWG | 5.26 | 0.116 in | 30 | 35 | 40 | 40 | 35 A(max 30 A breaker) |
| 8 AWG | 8.37 | 0.146 in | 40 | 50 | 55 | 55 | 50 A |
| 6 AWG | 13.30 | 0.184 in | 55 | 65 | 75 | 75 | 65 A |
| 4 AWG | 21.15 | 0.232 in | 70 | 85 | 95 | 95 | 85 A |
| 3 AWG | 26.66 | 0.260 in | 85 | 100 | 115 | 115 | 100 A |
| 2 AWG | 33.62 | 0.292 in | 95 | 115 | 130 | 130 | 115 A |
| 1 AWG | 42.41 | 0.332 in | 110 | 130 | 145 | 145 | 130 A |
| 1/0 AWG | 53.51 | 0.372 in | 125 | 150 | 170 | 170 | 150 A |
| 2/0 AWG | 67.44 | 0.418 in | 145 | 175 | 195 | 195 | 175 A |
| 3/0 AWG | 85.02 | 0.470 in | 165 | 200 | 225 | 225 | 200 A |
| 4/0 AWG | 107.22 | 0.528 in | 195 | 230 | 260 | 260 | 230 A |
| 250 kcmil | 126.67 | 0.575 in | 215 | 255 | 290 | 290 | 255 A |
| 300 kcmil | 152.01 | 0.630 in | 240 | 285 | 320 | 320 | 285 A |
| 350 kcmil | 177.34 | 0.681 in | 260 | 310 | 350 | 350 | 310 A |
| 400 kcmil | 202.68 | 0.728 in | 280 | 335 | 380 | 380 | 335 A |
| 500 kcmil | 253.35 | 0.813 in | 320 | 380 | 430 | 430 | 380 A |
| 600 kcmil | 304.02 | 0.893 in | 350 | 420 | 475 | 475 | 420 A |
| 700 kcmil | 354.69 | 0.964 in | 385 | 460 | 520 | 520 | 460 A |
| 750 kcmil | 380.03 | 0.998 in | 400 | 475 | 535 | 535 | 475 A |
| 800 kcmil | 405.36 | 1.030 in | 410 | 490 | 555 | 555 | 490 A |
| 900 kcmil | 456.03 | 1.094 in | 435 | 520 | 585 | 585 | 520 A |
| 1000 kcmil | 506.70 | 1.152 in | 455 | 545 | 615 | 615 | 545 A |
- Table 310.16 assumes conductors in a raceway, cable or directly buried, 30 °C ambient and up to three current-carrying conductors; ambient correction is from 310.15(B) and the adjustment for more conductors from 310.15(C)(1). Area is from the circular mils of Chapter 9 Table 8 and the diameter is the stranded conductor without insulation.
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
How it works
01
Choose copper or aluminum
Aluminum starts at 12 AWG; there is no 14 AWG aluminum building wire.
02
Set the conditions
Insulation and terminal rating, ambient temperature and conductors in the raceway.
03
Read the size
Area, diameter and the usable ampacity for each gauge.
Questions
Why do bigger AWG numbers mean thinner wire?
Can I hand the result to an inspector?
Do I need to sign up?
Common questions
- What size wire for a dryer?
- What size wire for a range?
- What size wire for a water heater?
- What size wire for a hot tub?
- Wire size chart: amps to AWG
- What size wire for a 15 amp circuit?
- What size wire for a 20 amp circuit?
- What size wire for 20 amps at 100 feet?
- What size wire for a 30 amp circuit?
- What size wire for a 40 amp circuit?
- What size wire for a 50 amp circuit?
- All wire, breaker and NEC answers
More NEC calculators
- Dwelling load calculatorService size by the NEC optional method
- EV charger load calculationCan my panel handle an EV charger or heat pump?
- Voltage drop calculatorDrop in volts and percent, and a wire size that carries the load
- Conduit fill calculatorFill percent and the smallest conduit size
- Box fill calculatorIs the electrical box big enough?
- Wire size calculatorAmps and distance in, minimum wire gauge out
- Wire ampacity chartNEC 310.16 with your corrections applied
- Ground wire size calculatorEquipment ground by 250.122, service ground by 250.66
- Transformer sizing calculatorkVA, full-load amps and 450.3(B) breaker sizes
- kVA to amps calculatorSingle- and three-phase, both directions
- Pull box calculatorPull and junction box size by 314.28
- Breaker size calculatorWatts or amps to breaker and wire size
- Panel scheduleCircuit directory and phase loads for a panel
Hand the inspector a clean calculation
Every calculator is free, with the full step-by-step result and NEC references on the page. Pro is US$9 a month for PDF reports with your company and the job address.