What size wire for a dryer?

Most electric dryers need a 30 A, 240 V circuit, and a 30 A circuit needs 10 AWG copper NM cable, 10 AWG copper THHN in conduit or 8 AWG aluminum. The size comes from NEC Table 310.16 and 240.4(D) for the full breaker rating, with NM cable at its 60 °C column (334.80). Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Always go by the breaker size on the appliance nameplate, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Minimum wire size for a dryer circuit
WiringMinimum size
30 A · Copper NM cable (Romex)60 °C column, as 334.80 requires for NM cable10 AWG copper
30 A · Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation10 AWG copper
30 A · Aluminum XHHW-2 or SER cable75 °C terminals, 90 °C insulation8 AWG aluminum

Dryer circuits in practice

Almost every electric dryer sold in the US plugs into a NEMA 14-30 receptacle on a 30 A, 240 V circuit, and its cord kit is bought separately. Gas dryers need only a 120 V receptacle for the drum motor and controls.

Stacked washer-dryer units and compact ventless dryers vary: some run at 120 V or on a 20 A circuit, so check the nameplate before running wire.

Wire size calculator
Circuit
A

Breaker rating or load current

ft
%

60 °C column, as 334.80 requires for NM cable

EV chargers, water heaters and similar: sized at 125 %.

Same circuit, other wiring

Copper NM cable (Romex)
10 AWG copper
Copper THHN/THWN-2 in conduit
10 AWG copper
Aluminum XHHW-2 or SER cable
8 AWG aluminum

30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.

Use at least 10 AWG copper

Carries 30.0 A and keeps the drop at 1.55 % over 50 ft, within 3 %.

NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop

Circuit

System
240 V single-phase
Conductor
10 AWG copper
Resistance
1.24 ohm/kft
One-way length
50 ft
Load current
30.0 A
Voltage drop
3.72 V
Voltage drop
1.55 %
Voltage at the load
236.3 V
Conductor ampacity needed at the terminals
30.0 A
10 AWG at the 60 °C column (terminals 60 °C, insulation 60 °C)
30.0 A
10 AWG at 60 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
30.0 A
Overcurrent protection for 10 AWG copper limited to
30 A
Smallest size for ampacity
10 AWG
Smallest size within 3 % drop
12 AWG
Recommended minimum size: the larger of the two
10 AWG copper
  • The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Can I plug a new dryer into an old 3-prong receptacle?

Where an existing 10-30 receptacle is already installed, the NEC still allows a 3-wire cord on it (250.140 Exception); a new circuit must be 4-wire.

Do I need a 4-wire cord and circuit?

For new installations, yes: since the 1996 NEC, ranges and dryers are connected with an insulated neutral and a separate equipment grounding conductor (250.140). Older 3-wire circuits may stay where they already exist.