What size wire for a hot tub?
Most hot tubs need a 40 A or 50 A, 240 V circuit with GFCI protection (680.44), and some large ones 60 A, and a 50 A circuit needs 8 AWG copper THHN in conduit. The size comes from NEC Table 310.16 and 240.4(D) for the full breaker rating. Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Always go by the breaker size on the appliance nameplate, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.
| Wiring | Minimum size |
|---|---|
| 50 A · Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation | 8 AWG copper |
| 40 A · Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation | 8 AWG copper |
| 60 A · Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation | 6 AWG copper |
Same circuit, other wiring
- Copper NM cable (Romex)
- 6 AWG copper
- Copper THHN/THWN-2 in conduit
- 8 AWG copper
- Aluminum XHHW-2 or SER cable
- 6 AWG aluminum
30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.
Use at least 8 AWG copper
Carries 50.0 A and keeps the drop at 1.62 % over 50 ft, within 3 %.
NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop
Circuit
- System
- 240 V single-phase
- Conductor
- 8 AWG copper
- Resistance
- Ch. 9 Table 8
- 0.778 ohm/kft
- One-way length
- 50 ft
- Load current
- 50.0 A
- Voltage drop
- 3.89 V
- Voltage drop
- 1.62 %
- Voltage at the load
- 236.1 V
- Conductor ampacity needed at the terminals
- 50.0 A
- 8 AWG at the 75 °C column (terminals 75 °C, insulation 90 °C)
- 110.14(C); 310.16
- 50.0 A
- 8 AWG at 90 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
- 310.15(B); 310.15(C)(1)
- 55.0 A
- Smallest size for ampacity
- 310.16
- 8 AWG
- Smallest size within 3 % drop
- 10 AWG
- Recommended minimum size: the larger of the two
- 8 AWG copper
- The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
Questions
What else does a hot tub circuit need?
More answers and calculators
- Dryer wire sizeWhat size wire for a dryer?
- Range wire sizeWhat size wire for a range?
- Water Heater wire sizeWhat size wire for a water heater?
- Wire size chartWire size chart: amps to AWG
- 10 gauge wire ampsHow many amps can 10 gauge wire carry?
- Dryer breaker sizeWhat size breaker for a dryer?
- Wire size calculatorAmps and distance in, minimum wire gauge out
- Voltage drop calculatorDrop in volts and percent, and a wire size that carries the load
- All answersEvery wire, breaker, ground and transformer question