Skip to content

Menu

What size wire for a hot tub?

Most hot tubs need a 40 A or 50 A, 240 V circuit with GFCI protection (680.44), and some large ones 60 A, and a 50 A circuit needs 8 AWG copper THHN in conduit. The size comes from NEC Table 310.16 and 240.4(D) for the full breaker rating. Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Always go by the breaker size on the appliance nameplate, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Minimum wire size for a hot tub circuit
WiringMinimum size
50 A · Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation8 AWG copper
40 A · Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation8 AWG copper
60 A · Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation6 AWG copper
Wire size calculator
Circuit
A

Breaker rating or load current

ft
%

75 °C terminals, 90 °C insulation

EV chargers, water heaters and similar: sized at 125 %.

Same circuit, other wiring

Copper NM cable (Romex)
6 AWG copper
Copper THHN/THWN-2 in conduit
8 AWG copper
Aluminum XHHW-2 or SER cable
6 AWG aluminum

30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.

Use at least 8 AWG copper

Carries 50.0 A and keeps the drop at 1.62 % over 50 ft, within 3 %.

NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop

Circuit

System
240 V single-phase
Conductor
8 AWG copper
Resistance
0.778 ohm/kft
One-way length
50 ft
Load current
50.0 A
Voltage drop
3.89 V
Voltage drop
1.62 %
Voltage at the load
236.1 V
Conductor ampacity needed at the terminals
50.0 A
8 AWG at the 75 °C column (terminals 75 °C, insulation 90 °C)
50.0 A
8 AWG at 90 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
55.0 A
Smallest size for ampacity
8 AWG
Smallest size within 3 % drop
10 AWG
Recommended minimum size: the larger of the two
8 AWG copper
  • The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

What else does a hot tub circuit need?

GFCI protection for the hot tub (680.44) and a maintenance disconnect within sight of it and at least 5 ft away (680.13). Outdoors most installers run copper THWN conductors with an insulated copper ground in conduit; NM cable is not allowed in wet or damp locations (334.12(B)).