What size breaker for a dryer?
An electric dryer needs a 30 A double-pole breaker at 240 V with 10 AWG copper wire, because dryers plug into a 30 A NEMA 14-30 receptacle and their nameplates call for a 30 A circuit. A typical 5,600 W element draws 23.3 A, which by itself needs at least a 25 A breaker (240.6(A)), and the wire must be one the breaker protects: 10 AWG copper under 240.4(D). Busbar's breaker size calculator below works out other loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Gas dryers need only a 120 V circuit for the motor and controls, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.
| Item | Size |
|---|---|
| 5,600 W at 240 V23.3 A, not a continuous load | 25 A minimum |
| Breaker the nameplate calls forNEMA 14-30 receptacle (110.3(B), 210.21(B)) | 30 A |
| Wire for 30 ANM cable, 60 °C column | 10 AWG copper |
25 A breaker with 10 AWG copper
Equipment that lists a maximum breaker or fuse on its nameplate (MOCP) must not be protected above it (110.3(B)).
NEC 210.20(A) · 240.6(A) · 240 V single-phase
Load
- Load current: 5,600 W ÷ 240 V
- 23.3 A
Breaker and wire
- Smallest standard breaker that carries it
- 240.6(A)
- 25 A
- Wire for that breaker: Copper NM cable (Romex), 60 °C column, as 334.80 requires for NM cable
- Table 310.16, 240.4(D)
- 10 AWG copper
- Equipment grounding conductor
- Table 250.122
- 10 AWG copper
- Motor, air-conditioning and heat pump circuits are sized from the nameplate minimum circuit ampacity and maximum overcurrent protection under Articles 430 and 440, not this way. Household ranges may use the demand of Table 220.55 (120.55 in NEC 2026), and storage water heaters of 120 gallons or less are continuous loads (422.13).
- The wire is sized so its ampacity is at least the breaker rating at 30 °C with no more than three current-carrying conductors; long runs may need a larger size for voltage drop.
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
Questions
Can I use a 40 amp breaker on a dryer?
Does a dryer need a 4-wire circuit?
More answers and calculators
- Water heater breaker sizeWhat size breaker for a water heater?
- Range breaker sizeWhat size breaker for an electric range?
- 100 A service wireWhat size wire for a 100 amp service?
- 200 A service ground wireWhat size ground wire for a 200 amp service?
- Breaker size calculatorWatts or amps to breaker and wire size
- Wire size calculatorAmps and distance in, minimum wire gauge out
- All answersEvery wire, breaker, ground and transformer question