What size breaker for a dryer?

An electric dryer needs a 30 A double-pole breaker at 240 V with 10 AWG copper wire, because dryers plug into a 30 A NEMA 14-30 receptacle and their nameplates call for a 30 A circuit. A typical 5,600 W element draws 23.3 A, which by itself needs at least a 25 A breaker (240.6(A)), and the wire must be one the breaker protects: 10 AWG copper under 240.4(D). Busbar's breaker size calculator below works out other loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Gas dryers need only a 120 V circuit for the motor and controls, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Electric dryer circuit
ItemSize
5,600 W at 240 V23.3 A, not a continuous load25 A minimum
Breaker the nameplate calls forNEMA 14-30 receptacle (110.3(B), 210.21(B))30 A
Wire for 30 ANM cable, 60 °C column10 AWG copper
Breaker size calculator
Load
W

From the nameplate

Water heaters, EV chargers, lighting left on: sized at 125 %.

60 °C column, as 334.80 requires for NM cable

25 A breaker with 10 AWG copper

Equipment that lists a maximum breaker or fuse on its nameplate (MOCP) must not be protected above it (110.3(B)).

NEC 210.20(A) · 240.6(A) · 240 V single-phase

Load

Load current: 5,600 W ÷ 240 V
23.3 A

Breaker and wire

Smallest standard breaker that carries it
25 A
Wire for that breaker: Copper NM cable (Romex), 60 °C column, as 334.80 requires for NM cable
10 AWG copper
Equipment grounding conductor
10 AWG copper
  • Motor, air-conditioning and heat pump circuits are sized from the nameplate minimum circuit ampacity and maximum overcurrent protection under Articles 430 and 440, not this way. Household ranges may use the demand of Table 220.55 (120.55 in NEC 2026), and storage water heaters of 120 gallons or less are continuous loads (422.13).
  • The wire is sized so its ampacity is at least the breaker rating at 30 °C with no more than three current-carrying conductors; long runs may need a larger size for voltage drop.
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Can I use a 40 amp breaker on a dryer?

No. The 30 A receptacle and the dryer's nameplate limit the circuit to 30 A, and 10 AWG copper wire may not be protected above 30 A (240.4(D)).

Does a dryer need a 4-wire circuit?

For new installations, yes: two hots, an insulated neutral and an equipment grounding conductor to a 14-30 receptacle (250.140). Existing 3-wire 10-30 circuits may stay.