What size breaker for an electric range?

Most electric ranges and stoves up to about 16 kW need a 40 A double-pole breaker at 240 V with 8 AWG copper; use 50 A with 6 AWG copper if the nameplate calls for it. The NEC lets one range be counted at its Table 220.55 demand, 8 kW for a range of 12 kW or less (33.3 A), and sets a 40 A minimum for ranges of 8¾ kW or more (210.19(A)(3)); Table 220.55 is 120.55 in NEC 2026. Busbar's breaker size calculator below works out other loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Wall ovens and cooktops on their own circuits follow their nameplates, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Breaker for one household range at 240 V
NameplateBreakerCopper NM
8 kWColumn B demand 6.4 kW = 26.7 A30 A10 AWG copper
10 kWColumn C demand 8.0 kW = 33.3 A40 A8 AWG copper
12 kWColumn C demand 8.0 kW = 33.3 A40 A8 AWG copper
14 kWColumn C demand 8.8 kW = 36.7 A40 A8 AWG copper
16 kWColumn C demand 9.6 kW = 40.0 A40 A8 AWG copper
Wire size calculator
Circuit
A

Breaker rating or load current

ft
%

60 °C column, as 334.80 requires for NM cable

EV chargers, water heaters and similar: sized at 125 %.

Same circuit, other wiring

Copper NM cable (Romex)
8 AWG copper
Copper THHN/THWN-2 in conduit
8 AWG copper
Aluminum XHHW-2 or SER cable
8 AWG aluminum

30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.

Use at least 8 AWG copper

Carries 40.0 A and keeps the drop at 1.30 % over 50 ft, within 3 %.

NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop

Circuit

System
240 V single-phase
Conductor
8 AWG copper
Resistance
0.778 ohm/kft
One-way length
50 ft
Load current
40.0 A
Voltage drop
3.11 V
Voltage drop
1.30 %
Voltage at the load
236.9 V
Conductor ampacity needed at the terminals
40.0 A
8 AWG at the 60 °C column (terminals 60 °C, insulation 60 °C)
40.0 A
8 AWG at 60 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
40.0 A
Smallest size for ampacity
8 AWG
Smallest size within 3 % drop
10 AWG
Recommended minimum size: the larger of the two
8 AWG copper
  • The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Why is the breaker smaller than the nameplate amps?

Burners and the oven rarely all run at full power together, so Table 220.55 allows a demand of 8 kW for one range of up to 12 kW, plus 5 % for each kW above that. The nameplate may still ask for a larger circuit; follow it (110.3(B)).

Can I use 6 AWG on a 40 amp range circuit?

Yes. A larger wire than the minimum is always allowed, and it leaves room for a 50 A range later.