What size breaker for an electric range?
Most electric ranges and stoves up to about 16 kW need a 40 A double-pole breaker at 240 V with 8 AWG copper; use 50 A with 6 AWG copper if the nameplate calls for it. The NEC lets one range be counted at its Table 220.55 demand, 8 kW for a range of 12 kW or less (33.3 A), and sets a 40 A minimum for ranges of 8¾ kW or more (210.19(A)(3)); Table 220.55 is 120.55 in NEC 2026. Busbar's breaker size calculator below works out other loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Wall ovens and cooktops on their own circuits follow their nameplates, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.
| Nameplate | Breaker | Copper NM |
|---|---|---|
| 8 kWColumn B demand 6.4 kW = 26.7 A | 30 A | 10 AWG copper |
| 10 kWColumn C demand 8.0 kW = 33.3 A | 40 A | 8 AWG copper |
| 12 kWColumn C demand 8.0 kW = 33.3 A | 40 A | 8 AWG copper |
| 14 kWColumn C demand 8.8 kW = 36.7 A | 40 A | 8 AWG copper |
| 16 kWColumn C demand 9.6 kW = 40.0 A | 40 A | 8 AWG copper |
Same circuit, other wiring
- Copper NM cable (Romex)
- 8 AWG copper
- Copper THHN/THWN-2 in conduit
- 8 AWG copper
- Aluminum XHHW-2 or SER cable
- 8 AWG aluminum
30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.
Use at least 8 AWG copper
Carries 40.0 A and keeps the drop at 1.30 % over 50 ft, within 3 %.
NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop
Circuit
- System
- 240 V single-phase
- Conductor
- 8 AWG copper
- Resistance
- Ch. 9 Table 8
- 0.778 ohm/kft
- One-way length
- 50 ft
- Load current
- 40.0 A
- Voltage drop
- 3.11 V
- Voltage drop
- 1.30 %
- Voltage at the load
- 236.9 V
- Conductor ampacity needed at the terminals
- 40.0 A
- 8 AWG at the 60 °C column (terminals 60 °C, insulation 60 °C)
- 110.14(C); 310.16
- 40.0 A
- 8 AWG at 60 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
- 310.15(B); 310.15(C)(1)
- 40.0 A
- Smallest size for ampacity
- 310.16
- 8 AWG
- Smallest size within 3 % drop
- 10 AWG
- Recommended minimum size: the larger of the two
- 8 AWG copper
- The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
Questions
Why is the breaker smaller than the nameplate amps?
Can I use 6 AWG on a 40 amp range circuit?
More answers and calculators
- Dryer breaker sizeWhat size breaker for a dryer?
- Water heater breaker sizeWhat size breaker for a water heater?
- 100 A service wireWhat size wire for a 100 amp service?
- 200 A service ground wireWhat size ground wire for a 200 amp service?
- Breaker size calculatorWatts or amps to breaker and wire size
- Wire size calculatorAmps and distance in, minimum wire gauge out
- All answersEvery wire, breaker, ground and transformer question