What size breaker for a water heater?

A standard 4,500 W, 240 V electric water heater needs at least a 25 A double-pole breaker with 10 AWG copper, and many are wired at 30 A with 10 AWG copper. It draws 18.8 A, and because NEC 422.13 treats a storage water heater of 120 gallons or less as a continuous load, the breaker must be at least 125 % of that, 23.4 A, rounded up to a standard size (240.6(A)). Busbar's breaker size calculator below works out other loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Go by the wattage on the nameplate, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Breaker and wire for a 240 V storage water heater
NameplateBreakerCopper NM
3,500 W14.6 A × 125 % = 18.2 A20 A12 AWG copper
4,500 W18.8 A × 125 % = 23.4 A25 A10 AWG copper
5,500 W22.9 A × 125 % = 28.6 A30 A10 AWG copper
Breaker size calculator
Load
W

From the nameplate

Water heaters, EV chargers, lighting left on: sized at 125 %.

60 °C column, as 334.80 requires for NM cable

25 A breaker with 10 AWG copper

Equipment that lists a maximum breaker or fuse on its nameplate (MOCP) must not be protected above it (110.3(B)).

NEC 210.20(A) · 240.6(A) · 240 V single-phase

Load

Load current: 4,500 W ÷ 240 V
18.8 A
Continuous load (3 hours or more) × 125 %
23.4 A

Breaker and wire

Smallest standard breaker that carries it
25 A
Wire for that breaker: Copper NM cable (Romex), 60 °C column, as 334.80 requires for NM cable
10 AWG copper
Equipment grounding conductor
10 AWG copper
  • Motor, air-conditioning and heat pump circuits are sized from the nameplate minimum circuit ampacity and maximum overcurrent protection under Articles 430 and 440, not this way. Household ranges may use the demand of Table 220.55 (120.55 in NEC 2026), and storage water heaters of 120 gallons or less are continuous loads (422.13).
  • The wire is sized so its ampacity is at least the breaker rating at 30 °C with no more than three current-carrying conductors; long runs may need a larger size for voltage drop.
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Do both elements run at once?

In most residential water heaters the upper and lower elements are interlocked, so only one heats at a time and the nameplate wattage is the load. Check the nameplate if it lists simultaneous operation.

What about a tankless water heater?

Electric tankless heaters draw far more, often 100 A or more over two or three circuits. 422.13 does not cover them; follow the breaker and wire sizes in the installation manual.