What size breaker for a water heater?
A standard 4,500 W, 240 V electric water heater needs at least a 25 A double-pole breaker with 10 AWG copper, and many are wired at 30 A with 10 AWG copper. It draws 18.8 A, and because NEC 422.13 treats a storage water heater of 120 gallons or less as a continuous load, the breaker must be at least 125 % of that, 23.4 A, rounded up to a standard size (240.6(A)). Busbar's breaker size calculator below works out other loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Go by the wattage on the nameplate, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.
| Nameplate | Breaker | Copper NM |
|---|---|---|
| 3,500 W14.6 A × 125 % = 18.2 A | 20 A | 12 AWG copper |
| 4,500 W18.8 A × 125 % = 23.4 A | 25 A | 10 AWG copper |
| 5,500 W22.9 A × 125 % = 28.6 A | 30 A | 10 AWG copper |
25 A breaker with 10 AWG copper
Equipment that lists a maximum breaker or fuse on its nameplate (MOCP) must not be protected above it (110.3(B)).
NEC 210.20(A) · 240.6(A) · 240 V single-phase
Load
- Load current: 4,500 W ÷ 240 V
- 18.8 A
- Continuous load (3 hours or more) × 125 %
- 210.20(A)
- 23.4 A
Breaker and wire
- Smallest standard breaker that carries it
- 240.6(A)
- 25 A
- Wire for that breaker: Copper NM cable (Romex), 60 °C column, as 334.80 requires for NM cable
- Table 310.16, 240.4(D)
- 10 AWG copper
- Equipment grounding conductor
- Table 250.122
- 10 AWG copper
- Motor, air-conditioning and heat pump circuits are sized from the nameplate minimum circuit ampacity and maximum overcurrent protection under Articles 430 and 440, not this way. Household ranges may use the demand of Table 220.55 (120.55 in NEC 2026), and storage water heaters of 120 gallons or less are continuous loads (422.13).
- The wire is sized so its ampacity is at least the breaker rating at 30 °C with no more than three current-carrying conductors; long runs may need a larger size for voltage drop.
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
Questions
Do both elements run at once?
What about a tankless water heater?
More answers and calculators
- Dryer breaker sizeWhat size breaker for a dryer?
- Range breaker sizeWhat size breaker for an electric range?
- 100 A service wireWhat size wire for a 100 amp service?
- 200 A service ground wireWhat size ground wire for a 200 amp service?
- Breaker size calculatorWatts or amps to breaker and wire size
- Wire size calculatorAmps and distance in, minimum wire gauge out
- All answersEvery wire, breaker, ground and transformer question