What size wire for a 100 amp service?

A 100 A service to a one-family home needs 4 AWG copper or 2 AWG aluminum service-entrance conductors. NEC 310.12 applies to 100–400 A ratings and lets the conductors of a 120/240 V single-phase dwelling service, or of a feeder carrying the whole dwelling load, be sized at 83 % of the rating (83 A) using the 75 °C column of Table 310.16. Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. It does not apply to subpanels that carry only part of the load, or to three-phase or commercial services, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Minimum service-entrance conductors for 100 A (310.12)
WiringMinimum size
Copper75 °C column at 83 % of the rating4 AWG copper
Aluminum75 °C column at 83 % of the rating2 AWG aluminum

Is a 100 amp service enough?

A 100 A service is common in older and smaller homes, apartments and cabins, especially with gas heat, a gas range and a gas water heater. It gets tight once you add central air conditioning, an EV charger or a heat pump.

Before upgrading, check whether the existing service can take the new load with the twelve-month demand method of 220.87; it often can, with a load management device if needed.

To size the service itself from the house's loads, use the dwelling load calculator. The wire size calculator sizes branch circuits and subpanel feeders at their full rating, not at the 83 % of 310.12.

Questions

Is 100 amps enough for a house?

For a small house with gas appliances, usually yes. An all-electric house, or one adding an EV charger and heat pump, often needs 150 A or 200 A; a load calculation tells you rather than a rule of thumb.

Why is the wire smaller than the breaker rating?

Because a whole home rarely draws its full service rating, 310.12 allows 83 % of a 100–400 A rating for a single-phase dwelling service or the main feeder that carries the entire load. Every other feeder is sized at 100 % from Table 310.16.

Does the neutral need to be the same size?

Not always: the neutral is sized for the calculated unbalanced load (220.61) and may be smaller, but not below the grounding electrode conductor size in 250.24(C). Your utility may also set its own minimum.