What size wire for a 100 amp service?
A 100 A service to a one-family home needs 4 AWG copper or 2 AWG aluminum service-entrance conductors. NEC 310.12 applies to 100–400 A ratings and lets the conductors of a 120/240 V single-phase dwelling service, or of a feeder carrying the whole dwelling load, be sized at 83 % of the rating (83 A) using the 75 °C column of Table 310.16. Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. It does not apply to subpanels that carry only part of the load, or to three-phase or commercial services, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.
| Wiring | Minimum size |
|---|---|
| Copper75 °C column at 83 % of the rating | 4 AWG copper |
| Aluminum75 °C column at 83 % of the rating | 2 AWG aluminum |
Is a 100 amp service enough?
A 100 A service is common in older and smaller homes, apartments and cabins, especially with gas heat, a gas range and a gas water heater. It gets tight once you add central air conditioning, an EV charger or a heat pump.
Before upgrading, check whether the existing service can take the new load with the twelve-month demand method of 220.87; it often can, with a load management device if needed.
To size the service itself from the house's loads, use the dwelling load calculator. The wire size calculator sizes branch circuits and subpanel feeders at their full rating, not at the 83 % of 310.12.
Questions
Is 100 amps enough for a house?
Why is the wire smaller than the breaker rating?
Does the neutral need to be the same size?
More answers and calculators
- 60 A subpanel wireWhat size wire for a 60 amp subpanel?
- 100 A subpanel wireWhat size wire for a 100 amp subpanel?
- 150 A service wireWhat size wire for a 150 amp service?
- 200 A service wireWhat size wire for a 200 amp service?
- 200 A service ground wireWhat size ground wire for a 200 amp service?
- Outlets on 20 AHow many outlets can go on a 20 amp circuit?
- Dwelling load calculatorService size by the NEC optional method
- Wire size calculatorAmps and distance in, minimum wire gauge out
- All answersEvery wire, breaker, ground and transformer question