What size wire for a 150 amp service?

A 150 A service to a one-family home needs 1 AWG copper or 2/0 AWG aluminum service-entrance conductors. NEC 310.12 applies to 100–400 A ratings and lets the conductors of a 120/240 V single-phase dwelling service, or of a feeder carrying the whole dwelling load, be sized at 83 % of the rating (125 A) using the 75 °C column of Table 310.16. Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. It does not apply to subpanels that carry only part of the load, or to three-phase or commercial services, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Minimum service-entrance conductors for 150 A (310.12)
WiringMinimum size
Copper75 °C column at 83 % of the rating1 AWG copper
Aluminum75 °C column at 83 % of the rating2/0 AWG aluminum

When a 150 amp service makes sense

A 150 A service suits mid-size homes with central air and a few electric appliances, and it is a common upgrade from 100 A when the meter base and service entrance can stay in place.

If the house may add an EV charger or electric heat later, compare the cost of going straight to 200 A: the service-entrance cable is one or two sizes larger, but the panel and labor are much the same.

To size the service itself from the house's loads, use the dwelling load calculator. The wire size calculator sizes branch circuits and subpanel feeders at their full rating, not at the 83 % of 310.12.

Questions

Should I upgrade to 150 or 200 amps?

Run the load calculation first. If it lands well under 150 A, a 150 A service is fine; if it is close or you plan an EV charger, heat pump or hot tub, 200 A leaves room.

Why is the wire smaller than the breaker rating?

Because a whole home rarely draws its full service rating, 310.12 allows 83 % of a 100–400 A rating for a single-phase dwelling service or the main feeder that carries the entire load. Every other feeder is sized at 100 % from Table 310.16.

Does the neutral need to be the same size?

Not always: the neutral is sized for the calculated unbalanced load (220.61) and may be smaller, but not below the grounding electrode conductor size in 250.24(C). Your utility may also set its own minimum.