What size wire for a 100 amp subpanel?
A 100 A subpanel feeder needs 3 AWG copper or 1 AWG aluminum (SER cable or XHHW-2 in conduit) with 75 °C terminals. Feeders to a subpanel are sized at 100 % from NEC Table 310.16; the 83 % allowance of 310.12 is only for the service or a feeder carrying the whole dwelling load. Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Add a separate equipment grounding conductor and keep neutral and ground apart in the subpanel, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.
| Wiring | Minimum size |
|---|---|
| Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation | 3 AWG copper |
| Aluminum XHHW-2 or SER cable75 °C terminals, 90 °C insulation | 1 AWG aluminum |
What a 100 amp subpanel is for
A 100 A subpanel is the usual size for an addition, a finished basement, or a detached garage or workshop with an EV charger and power tools.
Long runs to outbuildings are where voltage drop matters most: at 150 ft or more the feeder often needs to be one or two sizes larger than the table, and the equipment ground grows in proportion.
In a finished basement or addition the subpanel is usually fed from the main panel with SER cable through the framing, while a detached building gets conduit or direct-burial cable in a trench.
Same circuit, other wiring
- Copper NM cable (Romex)
- 1 AWG copper
- Copper THHN/THWN-2 in conduit
- 3 AWG copper
- Aluminum XHHW-2 or SER cable
- 1 AWG aluminum
30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.
Use at least 3 AWG copper
Carries 100.0 A and keeps the drop at 1.02 % over 50 ft, within 3 %.
NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop
Circuit
- System
- 240 V single-phase
- Conductor
- 3 AWG copper
- Resistance
- Ch. 9 Table 8
- 0.245 ohm/kft
- One-way length
- 50 ft
- Load current
- 100.0 A
- Voltage drop
- 2.45 V
- Voltage drop
- 1.02 %
- Voltage at the load
- 237.6 V
- Conductor ampacity needed at the terminals
- 100.0 A
- 3 AWG at the 75 °C column (terminals 75 °C, insulation 90 °C)
- 110.14(C); 310.16
- 100.0 A
- 3 AWG at 90 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
- 310.15(B); 310.15(C)(1)
- 115.0 A
- Smallest size for ampacity
- 310.16
- 3 AWG
- Smallest size within 3 % drop
- 6 AWG
- Recommended minimum size: the larger of the two
- 3 AWG copper
- The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
Questions
Can I feed a 100 amp subpanel from a 200 amp panel?
Can I use the 83 % rule for a subpanel?
What about a detached garage far away?
More answers and calculators
- 60 A subpanel wireWhat size wire for a 60 amp subpanel?
- 100 A service wireWhat size wire for a 100 amp service?
- 150 A service wireWhat size wire for a 150 amp service?
- 200 A service wireWhat size wire for a 200 amp service?
- 200 A service ground wireWhat size ground wire for a 200 amp service?
- Outlets on 20 AHow many outlets can go on a 20 amp circuit?
- Dwelling load calculatorService size by the NEC optional method
- Wire size calculatorAmps and distance in, minimum wire gauge out
- All answersEvery wire, breaker, ground and transformer question