What size wire for a 60 amp subpanel?

A 60 A subpanel feeder needs 6 AWG copper or 4 AWG aluminum (SER cable or XHHW-2 in conduit) with 75 °C terminals. Feeders to a subpanel are sized at 100 % from NEC Table 310.16; the 83 % allowance of 310.12 is only for the service or a feeder carrying the whole dwelling load. Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Add a separate equipment grounding conductor and keep neutral and ground apart in the subpanel, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Minimum feeder size for a 60 A subpanel
WiringMinimum size
Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation6 AWG copper
Aluminum XHHW-2 or SER cable75 °C terminals, 90 °C insulation4 AWG aluminum

What a 60 amp subpanel is for

A 60 A subpanel suits a detached garage, shed or small workshop with lights, receptacles, a small air conditioner and perhaps one 240 V tool. It leaves little room for an EV charger, which alone would take most of it.

If the building is detached, it needs its own grounding electrode, such as two ground rods, and its own disconnect.

A 60 A feeder over a short distance can be 6 AWG copper THHN in conduit; buried runs to a shed often use direct-burial UF or conductors in PVC at the depths of Table 300.5.

Wire size calculator
Circuit
A

Breaker rating or load current

ft
%

75 °C terminals, 90 °C insulation

EV chargers, water heaters and similar: sized at 125 %.

Same circuit, other wiring

Copper NM cable (Romex)
4 AWG copper
Copper THHN/THWN-2 in conduit
6 AWG copper
Aluminum XHHW-2 or SER cable
4 AWG aluminum

30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.

Use at least 6 AWG copper

Carries 60.0 A and keeps the drop at 1.23 % over 50 ft, within 3 %.

NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop

Circuit

System
240 V single-phase
Conductor
6 AWG copper
Resistance
0.491 ohm/kft
One-way length
50 ft
Load current
60.0 A
Voltage drop
2.95 V
Voltage drop
1.23 %
Voltage at the load
237.1 V
Conductor ampacity needed at the terminals
60.0 A
6 AWG at the 75 °C column (terminals 75 °C, insulation 90 °C)
65.0 A
6 AWG at 90 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
75.0 A
Smallest size for ampacity
6 AWG
Smallest size within 3 % drop
8 AWG
Recommended minimum size: the larger of the two
6 AWG copper
  • The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Is 60 amps enough for a garage?

For lights, receptacles and hand tools, yes. With a 48 A EV charger, a welder or a heater, plan on 100 A instead.

Can I use the 83 % rule for a subpanel?

No. 310.12 applies only to the service conductors of a one-family dwelling or to a feeder that carries its entire load. A subpanel feeder is sized from Table 310.16 at its full rating.

What about a detached garage far away?

Over about 100 feet the feeder usually needs a larger size for voltage drop. Enter the one-way length in the calculator below.