What size wire for a 50 amp circuit?

For a 50 A circuit use 6 AWG copper if it is NM cable (Romex), 8 AWG copper THHN/THWN-2 in conduit where the breaker and equipment are rated 75 °C, or 6 AWG aluminum. These come from NEC Table 310.16 with the small-conductor limits of 240.4(D), sizing the wire for the full 50 A breaker rating. Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Long runs need a larger size for voltage drop, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Minimum wire size for a 50 A circuit
WiringMinimum size
Copper NM cable (Romex)60 °C column, as 334.80 requires for NM cable6 AWG copper
Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation8 AWG copper
Aluminum XHHW-2 or SER cable75 °C terminals, 90 °C insulation6 AWG aluminum

What 50 amp circuits feed

Fifty amps at 240 V feeds large electric ranges, EV chargers set to 40 A, NEMA 14-50 receptacles used for charging or for a 50 A RV hookup, most hot tubs and many welders. A 50 A RV receptacle is a four-wire, 120/240 V outlet, not the 240 V-only kind used for some welders.

Because 6 AWG copper NM is rated 55 A at 60 °C, it is the usual cable for a 50 A circuit in a house; in conduit with 75 °C terminals, 8 AWG THHN is enough for the wire itself.

Wire size calculator
Circuit
A

Breaker rating or load current

ft
%

60 °C column, as 334.80 requires for NM cable

EV chargers, water heaters and similar: sized at 125 %.

Same circuit, other wiring

Copper NM cable (Romex)
6 AWG copper
Copper THHN/THWN-2 in conduit
8 AWG copper
Aluminum XHHW-2 or SER cable
6 AWG aluminum

30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.

Use at least 6 AWG copper

Carries 50.0 A and keeps the drop at 1.02 % over 50 ft, within 3 %.

NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop

Circuit

System
240 V single-phase
Conductor
6 AWG copper
Resistance
0.491 ohm/kft
One-way length
50 ft
Load current
50.0 A
Voltage drop
2.46 V
Voltage drop
1.02 %
Voltage at the load
237.5 V
Conductor ampacity needed at the terminals
50.0 A
6 AWG at the 60 °C column (terminals 60 °C, insulation 60 °C)
55.0 A
6 AWG at 60 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
55.0 A
Smallest size for ampacity
6 AWG
Smallest size within 3 % drop
10 AWG
Recommended minimum size: the larger of the two
6 AWG copper
  • The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Does a NEMA 14-50 outlet for an EV need GFCI protection?

Since NEC 2020, 125 V through 250 V receptacles in dwelling garages and outdoors need GFCI protection (210.8(A)), so a 14-50 in a garage usually needs a 50 A GFCI breaker. A hardwired charger has its own built-in protection.

Can I use 8 AWG copper for 50 amps?

Only where the conductor's 75 °C ampacity can be used: THHN or similar wire in conduit, with a breaker and equipment marked 75 °C (110.14(C)). NM cable is limited to the 60 °C column (334.80), so it needs 6 AWG.

Is 50 A wire the same for an EV charger?

An EV charger is a continuous load, so the circuit is sized at 125 % of the charger current: a 40 A charger needs a 50 A circuit. Turn on Continuous load in the calculator to check.

What about a long run?

Over roughly 50 to 100 feet, voltage drop usually decides the size, not ampacity. Enter the one-way length in the calculator below; it gives the larger of the ampacity size and the voltage drop size.