For a 70 A circuit use 4 AWG copper if it is NM cable (Romex), 4 AWG copper THHN/THWN-2 in conduit where the breaker and equipment are rated 75 °C, or 3 AWG aluminum. These come from NEC Table 310.16 with the small-conductor limits of 240.4(D), sizing the wire for the full 70 A breaker rating. Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Long runs need a larger size for voltage drop, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Minimum wire size for a 70 A circuit
WiringMinimum size
Copper NM cable (Romex)60 °C column, as 334.80 requires for NM cable4 AWG copper
Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation4 AWG copper
Aluminum XHHW-2 or SER cable75 °C terminals, 90 °C insulation3 AWG aluminum

What 70 amp circuits feed

Seventy amps is a less common size. It is what an EV charger set to 56 A needs, it suits heat pump air handlers with about 12 kW of strip heat and small electric boilers, and it is used for detached garages where a 60 A subpanel is not quite enough.

At this size the 60 °C and 75 °C columns diverge: as NM cable 4 AWG copper is rated exactly 70 A, while THHN in conduit with 75 °C terminals carries 85 A on the same size.

Because 70 A breakers are less common in residential panels, check that your panel maker offers one in the right type before planning the circuit.

Wire size calculator
Circuit
A

Breaker rating or load current

ft
%

60 °C column, as 334.80 requires for NM cable

EV chargers, water heaters and similar: sized at 125 %.

Same circuit, other wiring

Copper NM cable (Romex)
4 AWG copper
Copper THHN/THWN-2 in conduit
4 AWG copper
Aluminum XHHW-2 or SER cable
3 AWG aluminum

30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.

Use at least 4 AWG copper

Carries 70.0 A and keeps the drop at 0.90 % over 50 ft, within 3 %.

NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop

Circuit

System
240 V single-phase
Conductor
4 AWG copper
Resistance
0.308 ohm/kft
One-way length
50 ft
Load current
70.0 A
Voltage drop
2.16 V
Voltage drop
0.90 %
Voltage at the load
237.8 V
Conductor ampacity needed at the terminals
70.0 A
4 AWG at the 60 °C column (terminals 60 °C, insulation 60 °C)
70.0 A
4 AWG at 60 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
70.0 A
Smallest size for ampacity
4 AWG
Smallest size within 3 % drop
8 AWG
Recommended minimum size: the larger of the two
4 AWG copper
  • The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Is 4 AWG copper good for 70 amps?

Yes. 4 AWG copper carries 70 A as NM cable (60 °C column) and 85 A as THHN with 75 °C terminals, so it suits a 70 A breaker either way.

Can I use 4 AWG copper for 70 amps?

Only where the conductor's 75 °C ampacity can be used: THHN or similar wire in conduit, with a breaker and equipment marked 75 °C (110.14(C)). NM cable is limited to the 60 °C column (334.80), so it needs 4 AWG.

What about a long run?

Over roughly 50 to 100 feet, voltage drop usually decides the size, not ampacity. Enter the one-way length in the calculator below; it gives the larger of the ampacity size and the voltage drop size.