What size wire for an 80 amp circuit?

For an 80 A circuit use 3 AWG copper if it is NM cable (Romex), 4 AWG copper THHN/THWN-2 in conduit where the breaker and equipment are rated 75 °C, or 2 AWG aluminum. These come from NEC Table 310.16 with the small-conductor limits of 240.4(D), sizing the wire for the full 80 A breaker rating. Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Long runs need a larger size for voltage drop, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Minimum wire size for an 80 A circuit
WiringMinimum size
Copper NM cable (Romex)60 °C column, as 334.80 requires for NM cable3 AWG copper
Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation4 AWG copper
Aluminum XHHW-2 or SER cable75 °C terminals, 90 °C insulation2 AWG aluminum

What 80 amp circuits feed

An 80 A circuit is what an EV charger set to 64 A needs, the highest common Level 2 setting, because a charger counts at 125 %. It is also a common breaker for heat pump air handlers with 15 kW of strip heat and for subpanels in larger garages and additions.

3 AWG NM cable is hard to find, so many electricians use 2 AWG NM, THHN in conduit or SER cable at this rating.

For an EV charger at 64 A, the charger is usually hardwired rather than plugged in, since common receptacles stop at 50 A.

Wire size calculator
Circuit
A

Breaker rating or load current

ft
%

60 °C column, as 334.80 requires for NM cable

EV chargers, water heaters and similar: sized at 125 %.

Same circuit, other wiring

Copper NM cable (Romex)
3 AWG copper
Copper THHN/THWN-2 in conduit
4 AWG copper
Aluminum XHHW-2 or SER cable
2 AWG aluminum

30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.

Use at least 3 AWG copper

Carries 80.0 A and keeps the drop at 0.82 % over 50 ft, within 3 %.

NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop

Circuit

System
240 V single-phase
Conductor
3 AWG copper
Resistance
0.245 ohm/kft
One-way length
50 ft
Load current
80.0 A
Voltage drop
1.96 V
Voltage drop
0.82 %
Voltage at the load
238.0 V
Conductor ampacity needed at the terminals
80.0 A
3 AWG at the 60 °C column (terminals 60 °C, insulation 60 °C)
85.0 A
3 AWG at 60 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
85.0 A
Smallest size for ampacity
3 AWG
Smallest size within 3 % drop
8 AWG
Recommended minimum size: the larger of the two
3 AWG copper
  • The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Can I use 4 AWG for 80 amps?

As THHN in conduit with 75 °C terminals, yes: 4 AWG copper carries 85 A. As NM cable it is rated 70 A, so an 80 A breaker needs 3 AWG.

Can I use 4 AWG copper for 80 amps?

Only where the conductor's 75 °C ampacity can be used: THHN or similar wire in conduit, with a breaker and equipment marked 75 °C (110.14(C)). NM cable is limited to the 60 °C column (334.80), so it needs 3 AWG.

What about a long run?

Over roughly 50 to 100 feet, voltage drop usually decides the size, not ampacity. Enter the one-way length in the calculator below; it gives the larger of the ampacity size and the voltage drop size.