What size wire for an 80 amp circuit?
For an 80 A circuit use 3 AWG copper if it is NM cable (Romex), 4 AWG copper THHN/THWN-2 in conduit where the breaker and equipment are rated 75 °C, or 2 AWG aluminum. These come from NEC Table 310.16 with the small-conductor limits of 240.4(D), sizing the wire for the full 80 A breaker rating. Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Long runs need a larger size for voltage drop, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.
| Wiring | Minimum size |
|---|---|
| Copper NM cable (Romex)60 °C column, as 334.80 requires for NM cable | 3 AWG copper |
| Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation | 4 AWG copper |
| Aluminum XHHW-2 or SER cable75 °C terminals, 90 °C insulation | 2 AWG aluminum |
What 80 amp circuits feed
An 80 A circuit is what an EV charger set to 64 A needs, the highest common Level 2 setting, because a charger counts at 125 %. It is also a common breaker for heat pump air handlers with 15 kW of strip heat and for subpanels in larger garages and additions.
3 AWG NM cable is hard to find, so many electricians use 2 AWG NM, THHN in conduit or SER cable at this rating.
For an EV charger at 64 A, the charger is usually hardwired rather than plugged in, since common receptacles stop at 50 A.
Same circuit, other wiring
- Copper NM cable (Romex)
- 3 AWG copper
- Copper THHN/THWN-2 in conduit
- 4 AWG copper
- Aluminum XHHW-2 or SER cable
- 2 AWG aluminum
30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.
Use at least 3 AWG copper
Carries 80.0 A and keeps the drop at 0.82 % over 50 ft, within 3 %.
NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop
Circuit
- System
- 240 V single-phase
- Conductor
- 3 AWG copper
- Resistance
- Ch. 9 Table 8
- 0.245 ohm/kft
- One-way length
- 50 ft
- Load current
- 80.0 A
- Voltage drop
- 1.96 V
- Voltage drop
- 0.82 %
- Voltage at the load
- 238.0 V
- Conductor ampacity needed at the terminals
- 80.0 A
- 3 AWG at the 60 °C column (terminals 60 °C, insulation 60 °C)
- 110.14(C); 310.16
- 85.0 A
- 3 AWG at 60 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
- 310.15(B); 310.15(C)(1)
- 85.0 A
- Smallest size for ampacity
- 310.16
- 3 AWG
- Smallest size within 3 % drop
- 8 AWG
- Recommended minimum size: the larger of the two
- 3 AWG copper
- The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
Questions
Can I use 4 AWG for 80 amps?
Can I use 4 AWG copper for 80 amps?
What about a long run?
More answers and calculators
- Wire for 50 ampsWhat size wire for a 50 amp circuit?
- Wire for 60 ampsWhat size wire for a 60 amp circuit?
- Wire for 70 ampsWhat size wire for a 70 amp circuit?
- Wire for 100 ampsWhat size wire for a 100 amp circuit?
- 10 gauge wire ampsHow many amps can 10 gauge wire carry?
- Dryer breaker sizeWhat size breaker for a dryer?
- Wire size calculatorAmps and distance in, minimum wire gauge out
- Voltage drop calculatorDrop in volts and percent, and a wire size that carries the load
- All answersEvery wire, breaker, ground and transformer question