What size wire for a 100 amp circuit?

For a 100 A circuit or feeder use 3 AWG copper THHN/THWN-2 in conduit or 1 AWG aluminum (SER cable or XHHW-2), with the breaker and equipment rated 75 °C; NM cable is not made that large (334.104). The size comes from the 75 °C column of NEC Table 310.16 for the full 100 A breaker rating, while a whole-house 100 A service may use the smaller size of the 83 % rule in 310.12. Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Long runs need a larger size for voltage drop, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Minimum wire size for a 100 A circuit
WiringMinimum size
Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation3 AWG copper
Aluminum XHHW-2 or SER cable75 °C terminals, 90 °C insulation1 AWG aluminum

Where 100 amp circuits are used

A 100 A breaker usually feeds a subpanel for a garage, an addition or a detached workshop, or it is the main breaker of a small house, cabin or manufactured home. NM cable is not made this large, so these feeders are SER cable or THHN and XHHW-2 in conduit.

Remember the difference between a feeder and a service: the conductors of a whole-house 100 A service may be sized at 83 % of the rating, a subpanel feeder may not.

Wire size calculator
Circuit
A

Breaker rating or load current

ft
%

75 °C terminals, 90 °C insulation

EV chargers, water heaters and similar: sized at 125 %.

Same circuit, other wiring

Copper NM cable (Romex)
1 AWG copper
Copper THHN/THWN-2 in conduit
3 AWG copper
Aluminum XHHW-2 or SER cable
1 AWG aluminum

30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.

Use at least 3 AWG copper

Carries 100.0 A and keeps the drop at 1.02 % over 50 ft, within 3 %.

NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop

Circuit

System
240 V single-phase
Conductor
3 AWG copper
Resistance
0.245 ohm/kft
One-way length
50 ft
Load current
100.0 A
Voltage drop
2.45 V
Voltage drop
1.02 %
Voltage at the load
237.6 V
Conductor ampacity needed at the terminals
100.0 A
3 AWG at the 75 °C column (terminals 75 °C, insulation 90 °C)
100.0 A
3 AWG at 90 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
115.0 A
Smallest size for ampacity
3 AWG
Smallest size within 3 % drop
6 AWG
Recommended minimum size: the larger of the two
3 AWG copper
  • The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Is a 100 amp subpanel feeder the same as a 100 amp service?

No. A one-family service, or a feeder that carries the entire house load, may use the 83 % rule of 310.12; a subpanel feeder carries only part of the load and is sized at its full rating from Table 310.16.

Why not 1 AWG NM cable?

NM cable (Romex) is made only up to 2 AWG copper (334.104), which carries 95 A in its 60 °C column. Larger circuits use SER cable or single conductors in conduit.

What about a long run?

Over roughly 50 to 100 feet, voltage drop usually decides the size, not ampacity. Enter the one-way length in the calculator below; it gives the larger of the ampacity size and the voltage drop size.