What size wire for a 125 amp circuit?

For a 125 A circuit or feeder use 1 AWG copper THHN/THWN-2 in conduit or 2/0 AWG aluminum (SER cable or XHHW-2), with the breaker and equipment rated 75 °C; NM cable is not made that large (334.104). The size comes from the 75 °C column of NEC Table 310.16 for the full 125 A breaker rating, while a whole-house 125 A service may use the smaller size of the 83 % rule in 310.12. Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Long runs need a larger size for voltage drop, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Minimum wire size for a 125 A circuit
WiringMinimum size
Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation1 AWG copper
Aluminum XHHW-2 or SER cable75 °C terminals, 90 °C insulation2/0 AWG aluminum

Where 125 amp circuits are used

A 125 A breaker is a common main for condos, small homes and meter-main combinations, and a common feeder for subpanels in houses that add an EV charger and a heat pump. It also feeds large electric boilers and commercial kitchen equipment.

At this size aluminum SER cable or XHHW-2 is usually cheaper than copper and easier to pull, as long as the terminals are listed for aluminum and torqued to the marked value.

Wire size calculator
Circuit
A

Breaker rating or load current

ft
%

75 °C terminals, 90 °C insulation

EV chargers, water heaters and similar: sized at 125 %.

Same circuit, other wiring

Copper NM cable (Romex)
1/0 AWG copper
Copper THHN/THWN-2 in conduit
1 AWG copper
Aluminum XHHW-2 or SER cable
2/0 AWG aluminum

30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.

Use at least 1 AWG copper

Carries 125.0 A and keeps the drop at 0.80 % over 50 ft, within 3 %.

NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop

Circuit

System
240 V single-phase
Conductor
1 AWG copper
Resistance
0.154 ohm/kft
One-way length
50 ft
Load current
125.0 A
Voltage drop
1.93 V
Voltage drop
0.80 %
Voltage at the load
238.1 V
Conductor ampacity needed at the terminals
125.0 A
1 AWG at the 75 °C column (terminals 75 °C, insulation 90 °C)
130.0 A
1 AWG at 90 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
145.0 A
Smallest size for ampacity
1 AWG
Smallest size within 3 % drop
6 AWG
Recommended minimum size: the larger of the two
1 AWG copper
  • The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Can aluminum wire be used for a 125 amp feeder?

Yes. Aluminum conductors are common for feeders and services; use terminals marked AL or AL/CU, apply antioxidant where the maker calls for it and tighten to the torque on the equipment label (110.14(D)).

Why not 1/0 AWG NM cable?

NM cable (Romex) is made only up to 2 AWG copper (334.104), which carries 95 A in its 60 °C column. Larger circuits use SER cable or single conductors in conduit.

What about a long run?

Over roughly 50 to 100 feet, voltage drop usually decides the size, not ampacity. Enter the one-way length in the calculator below; it gives the larger of the ampacity size and the voltage drop size.