What size wire for a 150 amp circuit?

For a 150 A circuit or feeder use 1/0 AWG copper THHN/THWN-2 in conduit or 3/0 AWG aluminum (SER cable or XHHW-2), with the breaker and equipment rated 75 °C; NM cable is not made that large (334.104). The size comes from the 75 °C column of NEC Table 310.16 for the full 150 A breaker rating, while a whole-house 150 A service may use the smaller size of the 83 % rule in 310.12. Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Long runs need a larger size for voltage drop, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Minimum wire size for a 150 A circuit
WiringMinimum size
Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation1/0 AWG copper
Aluminum XHHW-2 or SER cable75 °C terminals, 90 °C insulation3/0 AWG aluminum

Where 150 amp circuits are used

A 150 A breaker feeds large subpanels, such as a detached garage with an EV charger and a workshop, or it is the main breaker of a mid-size house. Many 200 A panels feed a second panel through a 150 A breaker.

Feeders of this size run as SER cable, as XHHW-2 in conduit, or as direct-burial USE-2 conductors in a trench to an outbuilding.

Wire size calculator
Circuit
A

Breaker rating or load current

ft
%

75 °C terminals, 90 °C insulation

EV chargers, water heaters and similar: sized at 125 %.

Same circuit, other wiring

Copper NM cable (Romex)
3/0 AWG copper
Copper THHN/THWN-2 in conduit
1/0 AWG copper
Aluminum XHHW-2 or SER cable
3/0 AWG aluminum

30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.

Use at least 1/0 AWG copper

Carries 150.0 A and keeps the drop at 0.76 % over 50 ft, within 3 %.

NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop

Circuit

System
240 V single-phase
Conductor
1/0 AWG copper
Resistance
0.122 ohm/kft
One-way length
50 ft
Load current
150.0 A
Voltage drop
1.83 V
Voltage drop
0.76 %
Voltage at the load
238.2 V
Conductor ampacity needed at the terminals
150.0 A
1/0 AWG at the 75 °C column (terminals 75 °C, insulation 90 °C)
150.0 A
1/0 AWG at 90 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
170.0 A
Smallest size for ampacity
1/0 AWG
Smallest size within 3 % drop
4 AWG
Recommended minimum size: the larger of the two
1/0 AWG copper
  • The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Why is the subpanel wire bigger than a 150 amp service?

A one-family service may be sized at 83 % of its rating under 310.12, which allows 1 AWG copper for 150 A. A subpanel feeder is sized at 100 %, so it needs 1/0 AWG copper.

Why not 3/0 AWG NM cable?

NM cable (Romex) is made only up to 2 AWG copper (334.104), which carries 95 A in its 60 °C column. Larger circuits use SER cable or single conductors in conduit.

What about a long run?

Over roughly 50 to 100 feet, voltage drop usually decides the size, not ampacity. Enter the one-way length in the calculator below; it gives the larger of the ampacity size and the voltage drop size.