What size wire for a 150 amp circuit?
For a 150 A circuit or feeder use 1/0 AWG copper THHN/THWN-2 in conduit or 3/0 AWG aluminum (SER cable or XHHW-2), with the breaker and equipment rated 75 °C; NM cable is not made that large (334.104). The size comes from the 75 °C column of NEC Table 310.16 for the full 150 A breaker rating, while a whole-house 150 A service may use the smaller size of the 83 % rule in 310.12. Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. Long runs need a larger size for voltage drop, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.
| Wiring | Minimum size |
|---|---|
| Copper THHN/THWN-2 in conduit75 °C terminals, 90 °C insulation | 1/0 AWG copper |
| Aluminum XHHW-2 or SER cable75 °C terminals, 90 °C insulation | 3/0 AWG aluminum |
Where 150 amp circuits are used
A 150 A breaker feeds large subpanels, such as a detached garage with an EV charger and a workshop, or it is the main breaker of a mid-size house. Many 200 A panels feed a second panel through a 150 A breaker.
Feeders of this size run as SER cable, as XHHW-2 in conduit, or as direct-burial USE-2 conductors in a trench to an outbuilding.
Same circuit, other wiring
- Copper NM cable (Romex)
- 3/0 AWG copper
- Copper THHN/THWN-2 in conduit
- 1/0 AWG copper
- Aluminum XHHW-2 or SER cable
- 3/0 AWG aluminum
30 °C (86 °F) ambient, up to three current-carrying conductors. Use the voltage drop calculator for other conditions.
Use at least 1/0 AWG copper
Carries 150.0 A and keeps the drop at 0.76 % over 50 ft, within 3 %.
NEC Table 310.16 ampacity with 310.15 corrections, 110.14(C) and 240.4(D) · Chapter 9 Table 8 for voltage drop
Circuit
- System
- 240 V single-phase
- Conductor
- 1/0 AWG copper
- Resistance
- Ch. 9 Table 8
- 0.122 ohm/kft
- One-way length
- 50 ft
- Load current
- 150.0 A
- Voltage drop
- 1.83 V
- Voltage drop
- 0.76 %
- Voltage at the load
- 238.2 V
- Conductor ampacity needed at the terminals
- 150.0 A
- 1/0 AWG at the 75 °C column (terminals 75 °C, insulation 90 °C)
- 110.14(C); 310.16
- 150.0 A
- 1/0 AWG at 90 °C × 1 for 30 °C ambient × 1 for 3 current-carrying conductors
- 310.15(B); 310.15(C)(1)
- 170.0 A
- Smallest size for ampacity
- 310.16
- 1/0 AWG
- Smallest size within 3 % drop
- 4 AWG
- Recommended minimum size: the larger of the two
- 1/0 AWG copper
- The size is the larger of the smallest size for ampacity and the smallest size within the voltage drop target. Ampacity is from NEC Table 310.16 (30 °C ambient, up to three current-carrying conductors in a raceway or cable), corrected for ambient temperature per 310.15(B) and for more than three current-carrying conductors per 310.15(C)(1), with terminations limited per 110.14(C) and small conductors per 240.4(D).
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
Questions
Why is the subpanel wire bigger than a 150 amp service?
Why not 3/0 AWG NM cable?
What about a long run?
More answers and calculators
- Wire for 70 ampsWhat size wire for a 70 amp circuit?
- Wire for 80 ampsWhat size wire for an 80 amp circuit?
- Wire for 100 ampsWhat size wire for a 100 amp circuit?
- Wire for 125 ampsWhat size wire for a 125 amp circuit?
- 10 gauge wire ampsHow many amps can 10 gauge wire carry?
- Dryer breaker sizeWhat size breaker for a dryer?
- Wire size calculatorAmps and distance in, minimum wire gauge out
- Voltage drop calculatorDrop in volts and percent, and a wire size that carries the load
- All answersEvery wire, breaker, ground and transformer question