How many amps can 4 gauge wire carry?

4 AWG copper is rated 70 A in the 60 °C column, 85 A at 75 °C and 95 A at 90 °C, so it is a 70 A wire as NM cable and an 85 A wire as THHN with 75 °C terminals; 4 AWG aluminum carries 55, 65 and 75 A. These are NEC Table 310.16 values for no more than three current-carrying conductors at 30 °C (86 °F): NM cable must use the 60 °C column (334.80), and breakers and devices up to 100 A use it too unless they are marked 75 °C (110.14(C)). Busbar's ampacity chart below applies other temperatures and conductor counts for free; Pro is US$9 a month to download it as a PDF. Long runs may need a larger size for voltage drop, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Ampacity of 4 AWG wire, NEC Table 310.16
ConductorAmps
Copper, 60 °C columnNM cable (334.80); most terminals up to 100 A70 A
Copper, 75 °C columnTHHN in conduit with 75 °C terminals85 A
Copper, 90 °C columnStarting point for corrections only95 A
Aluminum, 75 °C columnXHHW-2 or SER cable65 A

Where 4 gauge wire is used

4 AWG copper feeds 70 A to 85 A circuits and small subpanels, and it is the copper size for a 100 A dwelling service under the 83 % rule of 310.12.

At this size aluminum becomes the more common choice for feeders: 2 AWG aluminum does much the same job for less money.

Wire ampacity chart
Conditions
°F
Copper ampacity, NEC Table 310.16, with corrections
Sizemm²Diameter60 °C75 °C90 °CCorrectedUsable
14 AWG2.080.073 in1520252520 A(max 15 A breaker)
12 AWG3.310.092 in2025303025 A(max 20 A breaker)
10 AWG5.260.116 in3035404035 A(max 30 A breaker)
8 AWG8.370.146 in4050555550 A
6 AWG13.300.184 in5565757565 A
4 AWG21.150.232 in7085959585 A
3 AWG26.660.260 in85100115115100 A
2 AWG33.620.292 in95115130130115 A
1 AWG42.410.332 in110130145145130 A
1/0 AWG53.510.372 in125150170170150 A
2/0 AWG67.440.418 in145175195195175 A
3/0 AWG85.020.470 in165200225225200 A
4/0 AWG107.220.528 in195230260260230 A
250 kcmil126.670.575 in215255290290255 A
300 kcmil152.010.630 in240285320320285 A
350 kcmil177.340.681 in260310350350310 A
400 kcmil202.680.728 in280335380380335 A
500 kcmil253.350.813 in320380430430380 A
600 kcmil304.020.893 in350420475475420 A
700 kcmil354.690.964 in385460520520460 A
750 kcmil380.030.998 in400475535535475 A
800 kcmil405.361.030 in410490555555490 A
900 kcmil456.031.094 in435520585585520 A
1000 kcmil506.701.152 in455545615615545 A
  • Table 310.16 assumes conductors in a raceway, cable or directly buried, 30 °C ambient and up to three current-carrying conductors; ambient correction is from 310.15(B) and the adjustment for more conductors from 310.15(C)(1). Area is from the circular mils of Chapter 9 Table 8 and the diameter is the stranded conductor without insulation.
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Can 4 gauge wire handle 100 amps?

Only as the service conductors of a one-family home, where 310.12 allows 83 % of the rating. For a 100 A subpanel feeder or circuit it falls short; use 3 AWG copper.

Can 4 gauge wire go on a 90 amp breaker?

Sometimes. 85 A is not a standard breaker size, so 240.4(B) allows the next size up, 90 A, where the circuit does not feed several receptacles for cord-and-plug loads and the conductors carry no more than 85 A of load. As NM cable the 60 °C column applies instead.

Why not use the 90 °C rating?

The 90 °C column of THHN is only the starting point for corrections for heat or more than three conductors in a raceway. The result may not exceed the column of the breaker and device terminals, usually 60 or 75 °C (110.14(C)).