How many amps can 6 gauge wire carry?
6 AWG copper is rated 55 A in the 60 °C column, 65 A at 75 °C and 75 A at 90 °C, so it is a 55 A wire as NM cable and a 65 A wire as THHN with 75 °C terminals; 6 AWG aluminum carries 40, 50 and 55 A. These are NEC Table 310.16 values for no more than three current-carrying conductors at 30 °C (86 °F): NM cable must use the 60 °C column (334.80), and breakers and devices up to 100 A use it too unless they are marked 75 °C (110.14(C)). Busbar's ampacity chart below applies other temperatures and conductor counts for free; Pro is US$9 a month to download it as a PDF. Long runs may need a larger size for voltage drop, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.
| Conductor | Amps |
|---|---|
| Copper, 60 °C columnNM cable (334.80); most terminals up to 100 A | 55 A |
| Copper, 75 °C columnTHHN in conduit with 75 °C terminals | 65 A |
| Copper, 90 °C columnStarting point for corrections only | 75 A |
| Aluminum, 75 °C columnXHHW-2 or SER cable | 50 A |
Where 6 gauge wire is used
6 AWG copper is the usual cable for 50 A circuits in a house, for 14-50 receptacles, hot tubs and large ranges, and as THHN for 60 A circuits and small subpanel feeders.
It is also the common grounding electrode conductor to ground rods, which never has to be larger than 6 AWG copper (250.66(A)).
| Size | mm² | Diameter | 60 °C | 75 °C | 90 °C | Corrected | Usable |
|---|---|---|---|---|---|---|---|
| 14 AWG | 2.08 | 0.073 in | 15 | 20 | 25 | 25 | 20 A(max 15 A breaker) |
| 12 AWG | 3.31 | 0.092 in | 20 | 25 | 30 | 30 | 25 A(max 20 A breaker) |
| 10 AWG | 5.26 | 0.116 in | 30 | 35 | 40 | 40 | 35 A(max 30 A breaker) |
| 8 AWG | 8.37 | 0.146 in | 40 | 50 | 55 | 55 | 50 A |
| 6 AWG | 13.30 | 0.184 in | 55 | 65 | 75 | 75 | 65 A |
| 4 AWG | 21.15 | 0.232 in | 70 | 85 | 95 | 95 | 85 A |
| 3 AWG | 26.66 | 0.260 in | 85 | 100 | 115 | 115 | 100 A |
| 2 AWG | 33.62 | 0.292 in | 95 | 115 | 130 | 130 | 115 A |
| 1 AWG | 42.41 | 0.332 in | 110 | 130 | 145 | 145 | 130 A |
| 1/0 AWG | 53.51 | 0.372 in | 125 | 150 | 170 | 170 | 150 A |
| 2/0 AWG | 67.44 | 0.418 in | 145 | 175 | 195 | 195 | 175 A |
| 3/0 AWG | 85.02 | 0.470 in | 165 | 200 | 225 | 225 | 200 A |
| 4/0 AWG | 107.22 | 0.528 in | 195 | 230 | 260 | 260 | 230 A |
| 250 kcmil | 126.67 | 0.575 in | 215 | 255 | 290 | 290 | 255 A |
| 300 kcmil | 152.01 | 0.630 in | 240 | 285 | 320 | 320 | 285 A |
| 350 kcmil | 177.34 | 0.681 in | 260 | 310 | 350 | 350 | 310 A |
| 400 kcmil | 202.68 | 0.728 in | 280 | 335 | 380 | 380 | 335 A |
| 500 kcmil | 253.35 | 0.813 in | 320 | 380 | 430 | 430 | 380 A |
| 600 kcmil | 304.02 | 0.893 in | 350 | 420 | 475 | 475 | 420 A |
| 700 kcmil | 354.69 | 0.964 in | 385 | 460 | 520 | 520 | 460 A |
| 750 kcmil | 380.03 | 0.998 in | 400 | 475 | 535 | 535 | 475 A |
| 800 kcmil | 405.36 | 1.030 in | 410 | 490 | 555 | 555 | 490 A |
| 900 kcmil | 456.03 | 1.094 in | 435 | 520 | 585 | 585 | 520 A |
| 1000 kcmil | 506.70 | 1.152 in | 455 | 545 | 615 | 615 | 545 A |
- Table 310.16 assumes conductors in a raceway, cable or directly buried, 30 °C ambient and up to three current-carrying conductors; ambient correction is from 310.15(B) and the adjustment for more conductors from 310.15(C)(1). Area is from the circular mils of Chapter 9 Table 8 and the diameter is the stranded conductor without insulation.
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
Questions
Is 6 gauge wire enough for a 60 amp subpanel?
Can 6 gauge wire go on a 70 amp breaker?
Why not use the 90 °C rating?
More answers and calculators
- 4 gauge wire ampsHow many amps can 4 gauge wire carry?
- 8 gauge wire ampsHow many amps can 8 gauge wire carry?
- 10 gauge wire ampsHow many amps can 10 gauge wire carry?
- 12 gauge wire ampsHow many amps can 12 gauge wire carry?
- Dryer breaker sizeWhat size breaker for a dryer?
- 100 A service wireWhat size wire for a 100 amp service?
- Wire ampacity chartNEC 310.16 with your corrections applied
- Wire size calculatorAmps and distance in, minimum wire gauge out
- All answersEvery wire, breaker, ground and transformer question