How many amps can 12 gauge wire carry?

12 AWG copper is rated 20 A in the 60 °C column, 25 A at 75 °C and 30 A at 90 °C, but 240.4(D) limits its breaker to 20 A, so in practice it is a 20 A wire; 12 AWG aluminum carries 15, 20 and 25 A but is limited to a 15 A breaker. These are NEC Table 310.16 values for no more than three current-carrying conductors at 30 °C (86 °F): NM cable must use the 60 °C column (334.80), and breakers and devices up to 100 A use it too unless they are marked 75 °C (110.14(C)). Busbar's ampacity chart below applies other temperatures and conductor counts for free; Pro is US$9 a month to download it as a PDF. Long runs may need a larger size for voltage drop, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Ampacity of 12 AWG wire, NEC Table 310.16
ConductorAmps
Copper, 60 °C columnNM cable (334.80); most terminals up to 100 A20 A
Copper, 75 °C columnTHHN in conduit with 75 °C terminals25 A
Copper, 90 °C columnStarting point for corrections only30 A
Largest breaker, copper240.4(D)20 A
Aluminum, 75 °C column240.4(D) limits the breaker to 15 A20 A

Where 12 gauge wire is used

12 AWG copper, usually in yellow NM cable, is the wire of 20 A circuits: kitchen countertop, bathroom, laundry and garage receptacles, and many general circuits in newer homes.

It is also the minimum many electricians use for long 15 A runs, because the heavier conductor keeps voltage drop down at the far end.

Its stiffness makes it harder to fold into crowded device boxes than 14 AWG; a deeper box or a 4 in square box with a mud ring helps, and box fill counts each 12 AWG conductor at 2.25 in³.

Wire ampacity chart
Conditions
°F
Copper ampacity, NEC Table 310.16, with corrections
Sizemm²Diameter60 °C75 °C90 °CCorrectedUsable
14 AWG2.080.073 in1520252520 A(max 15 A breaker)
12 AWG3.310.092 in2025303025 A(max 20 A breaker)
10 AWG5.260.116 in3035404035 A(max 30 A breaker)
8 AWG8.370.146 in4050555550 A
6 AWG13.300.184 in5565757565 A
4 AWG21.150.232 in7085959585 A
3 AWG26.660.260 in85100115115100 A
2 AWG33.620.292 in95115130130115 A
1 AWG42.410.332 in110130145145130 A
1/0 AWG53.510.372 in125150170170150 A
2/0 AWG67.440.418 in145175195195175 A
3/0 AWG85.020.470 in165200225225200 A
4/0 AWG107.220.528 in195230260260230 A
250 kcmil126.670.575 in215255290290255 A
300 kcmil152.010.630 in240285320320285 A
350 kcmil177.340.681 in260310350350310 A
400 kcmil202.680.728 in280335380380335 A
500 kcmil253.350.813 in320380430430380 A
600 kcmil304.020.893 in350420475475420 A
700 kcmil354.690.964 in385460520520460 A
750 kcmil380.030.998 in400475535535475 A
800 kcmil405.361.030 in410490555555490 A
900 kcmil456.031.094 in435520585585520 A
1000 kcmil506.701.152 in455545615615545 A
  • Table 310.16 assumes conductors in a raceway, cable or directly buried, 30 °C ambient and up to three current-carrying conductors; ambient correction is from 310.15(B) and the adjustment for more conductors from 310.15(C)(1). Area is from the circular mils of Chapter 9 Table 8 and the diameter is the stranded conductor without insulation.
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Can 12 gauge wire handle 25 amps?

Not on a 25 A breaker: 240.4(D) limits 12 AWG copper to 20 A. The 25 A figure in the 75 °C column is used only as a starting point for corrections.

Can 12 gauge wire go on a 25 amp breaker?

No. 240.4(D) caps 12 AWG copper at a 20 A breaker whatever the table column says. The exceptions are circuits the code sizes differently, such as motors and air-conditioning equipment with a nameplate maximum (240.4(G)).

Why not use the 90 °C rating?

The 90 °C column of THHN is only the starting point for corrections for heat or more than three conductors in a raceway. The result may not exceed the column of the breaker and device terminals, usually 60 or 75 °C (110.14(C)).