How many amps can 8 gauge wire carry?

8 AWG copper is rated 40 A in the 60 °C column, 50 A at 75 °C and 55 A at 90 °C, so it is a 40 A wire as NM cable and a 50 A wire as THHN with 75 °C terminals; 8 AWG aluminum carries 35, 40 and 45 A. These are NEC Table 310.16 values for no more than three current-carrying conductors at 30 °C (86 °F): NM cable must use the 60 °C column (334.80), and breakers and devices up to 100 A use it too unless they are marked 75 °C (110.14(C)). Busbar's ampacity chart below applies other temperatures and conductor counts for free; Pro is US$9 a month to download it as a PDF. Long runs may need a larger size for voltage drop, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Ampacity of 8 AWG wire, NEC Table 310.16
ConductorAmps
Copper, 60 °C columnNM cable (334.80); most terminals up to 100 A40 A
Copper, 75 °C columnTHHN in conduit with 75 °C terminals50 A
Copper, 90 °C columnStarting point for corrections only55 A
Aluminum, 75 °C columnXHHW-2 or SER cable40 A

Where 8 gauge wire is used

8 AWG copper is where the small-conductor breaker limits of 240.4(D) stop, so the table columns apply directly: 40 A as NM cable, 50 A as THHN with 75 °C terminals.

It is common for 40 A range and cooktop circuits, 32 A EV chargers, and as the conductor for 50 A circuits in conduit.

Wire ampacity chart
Conditions
°F
Copper ampacity, NEC Table 310.16, with corrections
Sizemm²Diameter60 °C75 °C90 °CCorrectedUsable
14 AWG2.080.073 in1520252520 A(max 15 A breaker)
12 AWG3.310.092 in2025303025 A(max 20 A breaker)
10 AWG5.260.116 in3035404035 A(max 30 A breaker)
8 AWG8.370.146 in4050555550 A
6 AWG13.300.184 in5565757565 A
4 AWG21.150.232 in7085959585 A
3 AWG26.660.260 in85100115115100 A
2 AWG33.620.292 in95115130130115 A
1 AWG42.410.332 in110130145145130 A
1/0 AWG53.510.372 in125150170170150 A
2/0 AWG67.440.418 in145175195195175 A
3/0 AWG85.020.470 in165200225225200 A
4/0 AWG107.220.528 in195230260260230 A
250 kcmil126.670.575 in215255290290255 A
300 kcmil152.010.630 in240285320320285 A
350 kcmil177.340.681 in260310350350310 A
400 kcmil202.680.728 in280335380380335 A
500 kcmil253.350.813 in320380430430380 A
600 kcmil304.020.893 in350420475475420 A
700 kcmil354.690.964 in385460520520460 A
750 kcmil380.030.998 in400475535535475 A
800 kcmil405.361.030 in410490555555490 A
900 kcmil456.031.094 in435520585585520 A
1000 kcmil506.701.152 in455545615615545 A
  • Table 310.16 assumes conductors in a raceway, cable or directly buried, 30 °C ambient and up to three current-carrying conductors; ambient correction is from 310.15(B) and the adjustment for more conductors from 310.15(C)(1). Area is from the circular mils of Chapter 9 Table 8 and the diameter is the stranded conductor without insulation.
  • This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.

Permit-ready PDF report

The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.

Pro, US$9/month

Questions

Can 8 gauge wire handle 50 amps?

As THHN in conduit with breaker and equipment terminals rated 75 °C, yes. As NM cable it is limited to its 60 °C rating, 40 A.

Can 8 gauge wire go on a 60 amp breaker?

No. Its 75 °C ampacity, 50 A, is already a standard breaker size, so 240.4(B) does not allow the next size up. As NM cable it is limited to 40 A.

Why not use the 90 °C rating?

The 90 °C column of THHN is only the starting point for corrections for heat or more than three conductors in a raceway. The result may not exceed the column of the breaker and device terminals, usually 60 or 75 °C (110.14(C)).