How many amps can 14 gauge wire carry?
14 AWG copper is rated 15 A in the 60 °C column, 20 A at 75 °C and 25 A at 90 °C, but 240.4(D) limits its breaker to 15 A, so in practice it is a 15 A wire; there is no 14 AWG aluminum building wire. These are NEC Table 310.16 values for no more than three current-carrying conductors at 30 °C (86 °F): NM cable must use the 60 °C column (334.80), and breakers and devices up to 100 A use it too unless they are marked 75 °C (110.14(C)). Busbar's ampacity chart below applies other temperatures and conductor counts for free; Pro is US$9 a month to download it as a PDF. Long runs may need a larger size for voltage drop, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.
| Conductor | Amps |
|---|---|
| Copper, 60 °C columnNM cable (334.80); most terminals up to 100 A | 15 A |
| Copper, 75 °C columnTHHN in conduit with 75 °C terminals | 20 A |
| Copper, 90 °C columnStarting point for corrections only | 25 A |
| Largest breaker, copper240.4(D) | 15 A |
Where 14 gauge wire is used
14 AWG copper is the wire of 15 A lighting and general receptacle circuits, usually in white NM cable. It is the smallest size normally used for branch circuits; smaller wire is for fixture leads, doorbells and thermostats.
Because the breaker limit, not the table, governs, a 14 AWG run must never end up on a 20 A breaker when a panel is changed or a circuit is extended.
| Size | mm² | Diameter | 60 °C | 75 °C | 90 °C | Corrected | Usable |
|---|---|---|---|---|---|---|---|
| 14 AWG | 2.08 | 0.073 in | 15 | 20 | 25 | 25 | 20 A(max 15 A breaker) |
| 12 AWG | 3.31 | 0.092 in | 20 | 25 | 30 | 30 | 25 A(max 20 A breaker) |
| 10 AWG | 5.26 | 0.116 in | 30 | 35 | 40 | 40 | 35 A(max 30 A breaker) |
| 8 AWG | 8.37 | 0.146 in | 40 | 50 | 55 | 55 | 50 A |
| 6 AWG | 13.30 | 0.184 in | 55 | 65 | 75 | 75 | 65 A |
| 4 AWG | 21.15 | 0.232 in | 70 | 85 | 95 | 95 | 85 A |
| 3 AWG | 26.66 | 0.260 in | 85 | 100 | 115 | 115 | 100 A |
| 2 AWG | 33.62 | 0.292 in | 95 | 115 | 130 | 130 | 115 A |
| 1 AWG | 42.41 | 0.332 in | 110 | 130 | 145 | 145 | 130 A |
| 1/0 AWG | 53.51 | 0.372 in | 125 | 150 | 170 | 170 | 150 A |
| 2/0 AWG | 67.44 | 0.418 in | 145 | 175 | 195 | 195 | 175 A |
| 3/0 AWG | 85.02 | 0.470 in | 165 | 200 | 225 | 225 | 200 A |
| 4/0 AWG | 107.22 | 0.528 in | 195 | 230 | 260 | 260 | 230 A |
| 250 kcmil | 126.67 | 0.575 in | 215 | 255 | 290 | 290 | 255 A |
| 300 kcmil | 152.01 | 0.630 in | 240 | 285 | 320 | 320 | 285 A |
| 350 kcmil | 177.34 | 0.681 in | 260 | 310 | 350 | 350 | 310 A |
| 400 kcmil | 202.68 | 0.728 in | 280 | 335 | 380 | 380 | 335 A |
| 500 kcmil | 253.35 | 0.813 in | 320 | 380 | 430 | 430 | 380 A |
| 600 kcmil | 304.02 | 0.893 in | 350 | 420 | 475 | 475 | 420 A |
| 700 kcmil | 354.69 | 0.964 in | 385 | 460 | 520 | 520 | 460 A |
| 750 kcmil | 380.03 | 0.998 in | 400 | 475 | 535 | 535 | 475 A |
| 800 kcmil | 405.36 | 1.030 in | 410 | 490 | 555 | 555 | 490 A |
| 900 kcmil | 456.03 | 1.094 in | 435 | 520 | 585 | 585 | 520 A |
| 1000 kcmil | 506.70 | 1.152 in | 455 | 545 | 615 | 615 | 545 A |
- Table 310.16 assumes conductors in a raceway, cable or directly buried, 30 °C ambient and up to three current-carrying conductors; ambient correction is from 310.15(B) and the adjustment for more conductors from 310.15(C)(1). Area is from the circular mils of Chapter 9 Table 8 and the diameter is the stranded conductor without insulation.
- This is not the professional advice of a licensed electrician. Check the result against the electrical code your jurisdiction enforces before you install anything.
Permit-ready PDF report
The same calculation with every NEC reference, your company and the job address, on US Letter. Saved in this browser only.
Questions
Can 14 gauge wire handle 20 amps?
Can 14 gauge wire go on a 20 amp breaker?
Why not use the 90 °C rating?
More answers and calculators
- 6 gauge wire ampsHow many amps can 6 gauge wire carry?
- 8 gauge wire ampsHow many amps can 8 gauge wire carry?
- 10 gauge wire ampsHow many amps can 10 gauge wire carry?
- 12 gauge wire ampsHow many amps can 12 gauge wire carry?
- Dryer breaker sizeWhat size breaker for a dryer?
- 100 A service wireWhat size wire for a 100 amp service?
- Wire ampacity chartNEC 310.16 with your corrections applied
- Wire size calculatorAmps and distance in, minimum wire gauge out