What size wire for a 400 amp service?

A 400 A service to a one-family home needs 400 kcmil copper or 600 kcmil aluminum service-entrance conductors. NEC 310.12 applies to 100–400 A ratings and lets the conductors of a 120/240 V single-phase dwelling service, or of a feeder carrying the whole dwelling load, be sized at 83 % of the rating (332 A) using the 75 °C column of Table 310.16. Busbar's wire size calculator checks other lengths, temperatures and continuous loads for free; Pro is US$9 a month for a PDF you can attach to a permit. It does not apply to subpanels that carry only part of the load, or to three-phase or commercial services, and it assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors, and it is not the professional advice of a licensed electrician: check your local electrical code before you install.

Minimum service-entrance conductors for 400 A (310.12)
WiringMinimum size
Copper75 °C column at 83 % of the rating400 kcmil copper
Aluminum75 °C column at 83 % of the rating600 kcmil aluminum

How a 400 amp service is built

A 400 A residential service is usually a 320 A continuous meter base feeding two 200 A panels, for large homes with several heat pumps, EV chargers, a pool or a workshop.

Each 200 A panel has its own feeder from the meter-main, sized at its full rating from Table 310.16, since it carries only part of the house load: 310.12 applies only to conductors that carry the entire dwelling load. Parallel sets of conductors are common on the service side.

To size the service itself from the house's loads, use the dwelling load calculator. The wire size calculator sizes branch circuits and subpanel feeders at their full rating, not at the 83 % of 310.12.

Questions

Is a 400 amp service one panel or two?

Usually two 200 A panels behind one meter base with two main breakers. A single 400 A panel exists, but it costs more and is less common in homes.

Why is the wire smaller than the breaker rating?

Because a whole home rarely draws its full service rating, 310.12 allows 83 % of a 100–400 A rating for a single-phase dwelling service or the main feeder that carries the entire load. Every other feeder is sized at 100 % from Table 310.16.

Does the neutral need to be the same size?

Not always: the neutral is sized for the calculated unbalanced load (220.61) and may be smaller, but not below the grounding electrode conductor size in 250.24(C). Your utility may also set its own minimum.